Electrical Application Details for App #: Z163080
Premises: 851 WEST END AVENUE MANHATTAN BIN: 1057156     Block: 1889   Lot: 60
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 851 W END AV Census Tract:   187 Health Area:  3110
SIDEWALK SHED Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   WEST 101 STREET,    WEST 102 STREET
Status:   C - JOB IS SIGNED OFF 12/20/2021
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/06/2017 2:11 PM
Application Entered:   10/06/2017 Job Start Date:   10/06/2017
Last Change:   12/20/2021 Job End Date:   10/06/2018
Appointment Status:   
Last Inspection By:   SHERON MEYERS       On     12/20/2021      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010940 Licensee Name: IVAN TORRES
Firm: 003484 Firm Name: 4000 ELECTRIC CORP
Firm Phone: 718-874-7270  Firm Address: 1244 OGDEN AVENUE BRONX NY 10452 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
W - SIDEWALK SHED WIRING & LIGHTING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BALWINDER SINGH
Owner Business Name: HKS CONSTRUCTION
Authorized Representative:  IVAN TORRES
Relationship To Owner:   SUB-CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND                   
Buildings Total                   
Total Units : 6 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/25/2020
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLATION OF WIRING AND LIGHTING 24 L.F.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z163080
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/20/2020 03/25/2020 DNM J (15) (0) Y
INSPECTION COMMENTS: SHED STILL PRESENT AT TIME OF INSPECTION, NO ACCESS TO BUILDING.
 
(2) 03/25/2020 03/25/2020 DNM V (15) (4)
INSPECTION COMMENTS: OBJECTIONS ISSUED.
 
(3) 12/20/2021 12/20/2021 SWR C R (30) (0)
INSPECTION COMMENTS: INSPECTION COMPLETE. SHED REMOVED BEFORE INSPECTION.

OBJECTION FOR APPLICATION #: Z163080
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
(GROUND FLOOR) DEFECTIVE LIGHTING FIXTURES IN USE (SHED)
RSLV 03/25/2020 03/25/2020 12/20/2021
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(GROUND FLOOR) FIXTURES, CONNECTORS, SHED IS NOT PROPERLY GROUNDED
RSLV 03/25/2020 03/25/2020 12/20/2021
 
003 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(GROUND FLOOR) KNOCKOUTS MISSING FROM OUTDOOR ROUND-BOX.(SHED)
RSLV 03/25/2020 03/25/2020 12/20/2021
 
004 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
(GROUND FLOOR) CONDUIT IS NOT PROPERLY SUPPORTED(SHED)
RSLV 03/25/2020 03/25/2020 12/20/2021