BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z162862
Premises: 2 RIVERSIDE BOULEVARD MANHATTAN BIN: 1089741     Block: 1171   Lot: 155
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 10 RIVERSIDE BLVD Census Tract:   151
GND FL Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10069 Community Board:   107
Special Place Name:   RIVERSIDE CENTER BUILDING 3
Related Job Number:    121192976
DOB Cross Street(s):   WEST 59 STREET,    WEST 61 STREET
Status:   C - JOB IS SIGNED OFF 11/17/2021
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   09/27/2017 Job Start Date:   09/19/2017
Last Change:   11/17/2021 Job End Date:   02/15/2019
Appointment Status:   
Last Inspection By:   ADAM ADAMSKI       On     11/16/2021      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011289 Licensee Name: PETER BORDUCCI
Firm: 002860 Firm Name: SOLAR ELEC. SYSTEMS, INC.
Firm Phone: 718-824-7000  Firm Address: 1402 BLONDELL AVENUE BRONX NY 10461 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $4,887.50
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (36  Stores, 288 Apartments)
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54549     Submittal #: 17A0171  
Owner / Occup:
Owner Business Name: RCB 3 NOMINEE LLC
Authorized Representative:  JOHN GAGNIER
Relationship To Owner:   REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  1-200A 1-400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  4  1-2500A 1-4000A 2-1600A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  6  6-4/0AL
D. Over 250 MCM  28  5-600 7-500 16-750 ALUM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  7  4-1200A 1-600A 2-1600A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL              600         
GND              180         
Buildings Total              780           
Total Units : 780 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 288 #4-Wire 1 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/27/2017 Notice: 1 - FIRST NOTICE 05/24/2021
Power Issued: 09/27/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  TWO NEW 4000A SERVICES AND FEEDERS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z162862
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/22/2021 05/24/2021 ASK V (240) (18)
INSPECTION COMMENTS: FAIL. INSPECTION COMPLETED. OBJECTION ISSUED. ATOI GIACOMO MARCHESE
 
(2) 11/16/2021 11/17/2021 ASK C R (120) (0)
INSPECTION COMMENTS: PASS. INSPECTION COMPLETED. ATOI JOSEPH.

OBJECTION FOR APPLICATION #: Z162862
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) PANIC HARDWARE MUST BE INSTALLED ART.110.26C2
RSLV 05/22/2021 05/22/2021 11/16/2021
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)CONTRACTOR NEEDS MARK ALL ELECTRIC EQUIPMENT ART.230.70B. 110.2
RSLV 05/22/2021 05/22/2021 11/16/2021
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) ARC FLASH LABEL NOT PROVIDED ART.110.16
RSLV 05/22/2021 05/22/2021 11/16/2021
 
004 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)TFSC FUSE TYPE AND SIZE NOT AS AB DRAWINGS ART.AM 110.2B
RSLV 05/22/2021 05/22/2021 11/16/2021
 
005 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)LINE SIDE OF FIRE PUMP CONTROLLER WIRING NOT AS PER AB DRAWINGS (MICABLE) ART AM.110.2B
RSLV 05/22/2021 05/22/2021 11/16/2021
 
006 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)LOAD BANK BREAKER SIZE NOT AS PER AB DRAWINGS ART AM. 110.2B
RSLV 05/22/2021 05/22/2021 11/16/2021
 
007 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) EMDS-GEN-1 NOT AS PER AB DRAWINGS ART.AM110.2B
RSLV 05/22/2021 05/22/2021 11/16/2021
 
008 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)FIRE ALARM SWITCH AFTER TRANSFORMER NOT AS PER AB DRAWINGS ART.AM110.2B
RSLV 05/22/2021 05/22/2021 11/16/2021
 
009 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) SERVICE NOT GROUNDED AS PER AB DRAWINGS ART. AM 110.2B
RSLV 05/22/2021 05/22/2021 11/16/2021
 
010 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)FIRE ALARM FUSE TYPE AND LINE SIDE WIRING SIZE NOT AS PER ABDRAWINGS ART.AM.110.2B
RSLV 05/22/2021 05/22/2021 11/16/2021
 
011 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) FP-1 FUSE TYPE NOT AS PER AB DRAWINGS ART.AM 110.2B
RSLV 05/22/2021 05/22/2021 11/16/2021
 
012 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) SHOW CORRECT WIRING FOR FP-2 ART.AM 110.2B
RSLV 05/22/2021 05/22/2021 11/16/2021
 
013 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)DISC-SC-1 FUSE SIZE NOT AS PER AB DRAWINGS ART.AM 110.2B
RSLV 05/22/2021 05/22/2021 11/16/2021
 
014 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)DISC-SC-5 FUSE SIZE NOT AS PER AB DRAWINGS ART.AM 110.2B
RSLV 05/22/2021 05/22/2021 11/16/2021
 
015 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)DLP-SC-1 FUSE AND LAYOUT NOT AS AB DRAWINGS ART.AM 110.2B
RSLV 05/22/2021 05/22/2021 11/16/2021
 
016 (325) ELECTRICAL CLOSETS SHALL NOT BE USED FOR OTHER PURPOSES
(ALL FLOORS) ELECTRIC ROOM STORAGE ART AM 110.25
RSLV 05/22/2021 05/22/2021 11/16/2021
 
017 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR) ROOM LAYOUT NOT AS PER AB DRAWINGS ART. AM . 110.2B
RSLV 05/22/2021 05/22/2021 11/16/2021
 
018 (279) WATER METER JUMPER IS MISSING/IMPROPER
(CELLAR) WATER METER JUMPER MISSING ART.250.53
RSLV 05/22/2021 05/22/2021 11/16/2021