| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
2 |
1-200A 1-400A |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
4 |
1-2500A 1-4000A 2-1600A |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
6 |
6-4/0AL |
| D. Over 250 MCM |
28 |
5-600 7-500 16-750 ALUM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
|
| D. 3 Phase Over 225 AMPS |
7 |
4-1200A 1-600A 2-1600A |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) PANIC HARDWARE MUST BE INSTALLED ART.110.26C2 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 002 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS)CONTRACTOR NEEDS MARK ALL ELECTRIC EQUIPMENT ART.230.70B. 110.2 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 003 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) ARC FLASH LABEL NOT PROVIDED ART.110.16 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 004 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)TFSC FUSE TYPE AND SIZE NOT AS AB DRAWINGS ART.AM 110.2B |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 005 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)LINE SIDE OF FIRE PUMP CONTROLLER WIRING NOT AS PER AB DRAWINGS (MICABLE) ART AM.110.2B |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 006 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)LOAD BANK BREAKER SIZE NOT AS PER AB DRAWINGS ART AM. 110.2B |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 007 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS) EMDS-GEN-1 NOT AS PER AB DRAWINGS ART.AM110.2B |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 008 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)FIRE ALARM SWITCH AFTER TRANSFORMER NOT AS PER AB DRAWINGS ART.AM110.2B |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 009 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS) SERVICE NOT GROUNDED AS PER AB DRAWINGS ART. AM 110.2B |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 010 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)FIRE ALARM FUSE TYPE AND LINE SIDE WIRING SIZE NOT AS PER ABDRAWINGS ART.AM.110.2B |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 011 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS) FP-1 FUSE TYPE NOT AS PER AB DRAWINGS ART.AM 110.2B |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 012 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS) SHOW CORRECT WIRING FOR FP-2 ART.AM 110.2B |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 013 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)DISC-SC-1 FUSE SIZE NOT AS PER AB DRAWINGS ART.AM 110.2B |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 014 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)DISC-SC-5 FUSE SIZE NOT AS PER AB DRAWINGS ART.AM 110.2B |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 015 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)DLP-SC-1 FUSE AND LAYOUT NOT AS AB DRAWINGS ART.AM 110.2B |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 016 |
(325) |
ELECTRICAL CLOSETS SHALL NOT BE USED FOR OTHER PURPOSES (ALL FLOORS) ELECTRIC ROOM STORAGE ART AM 110.25 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 017 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR) ROOM LAYOUT NOT AS PER AB DRAWINGS ART. AM . 110.2B |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 018 |
(279) |
WATER METER JUMPER IS MISSING/IMPROPER (CELLAR) WATER METER JUMPER MISSING ART.250.53 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |