| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
3 PHASE 400AMP |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
1 SETT 4 WIRE 500MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
10 |
MAIN LUG SPH 20 BRKT |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
200AMP 3PH MAIN BRKT |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (FLOOR: 004) NEW BREAKER ELECTRIC RANGE |
RSLV |
06/05/2019 |
06/05/2019 |
10/22/2019 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS) OUTLET BONES NOT BONDED 250.146 |
RSLV |
06/05/2019 |
06/05/2019 |
10/22/2019 |
| |
| 003 |
(999) |
OTHER (BASEMENT) 600 AMP SERVICE SW. DOOR MUST BE OPEN AT LEAST 90 110.26 |
RSLV |
06/05/2019 |
06/05/2019 |
10/22/2019 |
| |
| 004 |
(999) |
OTHER (BASEMENT) FIRE STOP REQUIRED CONDUITS 300.21 |
RSLV |
06/05/2019 |
06/05/2019 |
10/22/2019 |
| |
| 005 |
(999) |
OTHER (BASEMENT)PAA REQUIRED OBSERVED 4, SETS 350 SERVICE& FEEDERS CONDUCTORS, NEEDTO ADDED MORE LIGHTS, SWITCHES, RECEPTACLES, APTS. # 1, # 2 PUBLICHALLWAYS. |
RSLV |
06/05/2019 |
06/05/2019 |
10/22/2019 |