| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
200-AMP 3-POLE 4-WIRE |
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
3 X #3 AWG |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
4 X 3/0 AWG |
| D. Over 250 MCM |
0 |
|
| SUB FEEDERS (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
2 |
4X3/0 |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
24-CKT, 100A MLO |
| C. 3 Phase Up to 225 AMPS |
1 |
18-CKT, 225A MLO |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(124) |
TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE (CELLAR)240.21 TAP OF TAP, OLD FUSE PANEL (SEE RATING OF BUS ON PANEL OLDLABEL STATES 469AMP 110/208 VOLT OVER 10 FT. (AND COULD NOT GETACCESS TO FUSE FEEDING OLD BOARD |
RSLV |
09/07/2017 |
09/07/2017 |
10/20/2017 |
| |
| 002 |
(329) |
OPENINGS TO BE SEALED (CELLAR)300.21 FROM CELLAR TO PANEL LOCATIONS ALL PENETRATIONS MUST BEFILLED WHERE NECESSARY WITH FIRE STOPPING |
RSLV |
09/07/2017 |
09/07/2017 |
10/20/2017 |
| |
| 003 |
(999) |
OTHER (CELLAR)220 CONTRACTOR MUST PROVIDE LOAD LETTER FOR FUSE FEEDING THE OLDFUSE PANEL AND LOADS COMING OFF SHOW NEUTRAL LOAD SEPERATE DUE TOEXTENSION FROM 3 PHASE TO 1/PHASE PANELS |
RSLV |
09/07/2017 |
09/07/2017 |
10/20/2017 |
| |
| 004 |
(999) |
OTHER (CELLAR)110.14 ALTERATION OF EQUIPMENT AND PROVISIONS FOR TAP AGAINST ULLISTING OF ENCLOSURE PANEL IS ALSO TAPPED ON LOAD SIDE LUGS WITH 3ADDITIONAL SETS BY OTHERS |
RSLV |
09/07/2017 |
09/07/2017 |
10/20/2017 |
| |
| 005 |
(999) |
OTHER (CELLAR)2014 NYC BC 1022.4, 2008NYC BC 1019.1.2, 1968 NYC BC -375 (J)CONTRACTOR INSTALLED RISER IN EXIT ENCLOSURE PER M ABASSI NOTAPPROVED TO BE INSTALLED IN THE EXIT ENCLOSURE FROM THE CELLAR TOTHE FLOOR THE SERVICE IS UP TO |
RSLV |
09/07/2017 |
09/07/2017 |
10/20/2017 |