| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
#3 AWG |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
20 CK MAIN LUG PANEL |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(111) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (FLOOR: 014) NO WORKING SPACE FOR A/C DISCONNECT I N BATHROOM 110.26 |
RSLV |
10/16/2017 |
10/16/2017 |
01/16/2018 |
| |
| 002 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD (FLOOR: 014)KITCHEN CABINETS (TALL CABINETS) 120 V FLEX CORD PASSED THRU WALL400.8 |
RSLV |
10/16/2017 |
10/16/2017 |
01/16/2018 |
| |
| 003 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE (FLOOR: 014) HANGING KITCHEN LIGHT NOT GROUNDED 250.1 |
RSLV |
10/16/2017 |
10/16/2017 |
01/16/2018 |
| |
| 004 |
(999) |
OTHER (FLOOR: 014) BURIED PULL BOX FOR APT FEED AND BRANCH WIRING 314.29 |
RSLV |
10/16/2017 |
10/16/2017 |
01/16/2018 |
| |
| 005 |
(999) |
OTHER (FLOOR: 014) HANGING KITCHEN LIGT PENDING APPROVAL 110.3 |
RSLV |
10/16/2017 |
10/16/2017 |
01/16/2018 |
| |
| 006 |
(999) |
OTHER (FLOOR: 014) NO HANDLE TIES PROVIDED IN PANEL 210.4 |
RSLV |
10/16/2017 |
10/16/2017 |
01/16/2018 |
| |
| 007 |
(999) |
OTHER (FLOOR: 014) BURIED OUTLET FOR KITCHEN CABINETS 314.29 |
RSLV |
10/16/2017 |
10/16/2017 |
01/16/2018 |
| |
| 008 |
(999) |
OTHER (FLOOR: 014) BURIED LED DRIVER FOR KITCHEN CABINETS IN BACK 410.144 |
RSLV |
10/16/2017 |
10/16/2017 |
01/16/2018 |
| |
| 009 |
(261) |
ELECTRICAL CLOSETS/SERVICE ROOM IS USED FOR OTHER PURPOSES (BASEMENT) BSMT ELE ROOM |
RSLV |
10/16/2017 |
10/16/2017 |
01/16/2018 |