Electrical Application Details for App #: Z161873
Premises: 564 RIVERSIDE DRIVE MANHATTAN BIN: 1059891     Block: 1995   Lot: 63
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 560 RIVERSIDE DR Census Tract:   211 Health Area:  1400
10B Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10027 Community Board:   109
DOB Cross Street(s):   DEAD END,    12 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/27/2017 10:27 AM
Application Entered:   07/27/2017 Job Start Date:   07/27/2017
Last Change:   08/22/2025 Job End Date:   07/27/2018
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   ALGERNON CHARLES       On     09/24/2018      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012113 Licensee Name: DOMINICK CATELLO
Firm: 004170 Firm Name: LIVE WIRE ELECTRIC 1 LLC
Firm Phone: 718-605-9473  Firm Address: 516 INDUSTRIAL LOOP.#1D STATEN ISLAND NY 10309 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $55.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CLAUDIO MOREL
Authorized Representative:  LAZOJA SAMMY
Relationship To Owner:   ELECTRICAN


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  12/24 ML PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 09/24/2018
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  RELOCATION OF EXISTING PANEL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z161873
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/01/2018 02/01/2018 STP V (20) (3)
INSPECTION COMMENTS: FAIL. ADD FEEDER.
 
(2) 09/24/2018 09/24/2018 AYC V R (40) (4)
INSPECTION COMMENTS: FAIL

OBJECTION FOR APPLICATION #: Z161873
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 010) FMC NEEDS EQUIPMENT GROUND CONDUCTOR 250.118
RSLV 02/01/2018 02/01/2018 09/24/2018
 
002 (999) OTHER
(FLOOR: 010) DIRECTORY FOR PANEL 408.4
RSLV 02/01/2018 02/01/2018 09/24/2018
 
003 (999) OTHER
(FLOOR: 010) HANDLE TIES FOR SHARED NEUTRALS 210.4
RSLV 02/01/2018 02/01/2018 09/24/2018
 
004 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 010) CIRCUITS NOT IDENTIFIED IN THE PANEL. ART. 408.4
OPEN 09/24/2018 09/24/2018
 
005 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 010) BRANCH CIRCUIT WIRING NOT GROUPED. ART. 210.4(D)
OPEN 09/24/2018 09/24/2018
 
006 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 010) FMC MISSING GROUNDING CONDUCTOR. ART. 250.118
OPEN 09/24/2018 09/24/2018
 
007 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 010)HANDLES TIES MISSING ON MULTI-WIRED BRANCH CIRCUITS. ART. 210.4(B)
OPEN 09/24/2018 09/24/2018