| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
2 |
300A |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
7 |
|
| D. 3 Phase Over 225 AMPS |
6 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 11) |
FEEDER CONDUCTORS ARE NOT OF PROPER SIZE (FLOOR: 014)240.4 DB : 900 A FUSE ON 2 X 500 MCM TO DP ON21ST FL. |
RSLV |
07/10/2019 |
07/10/2019 |
08/01/2019 |
| |
| 002 |
(999) |
OTHER (FLOOR: 021) 300.21 NO FIRE STOP IN ELECTRIC CLOSET |
RSLV |
07/10/2019 |
07/10/2019 |
08/01/2019 |
| |
| 003 |
( 30) |
OUTLET BOXES ARE NOT SECURED (FLOOR: 024) 314.23 LED DRIVERS NOT SECURED |
RSLV |
07/10/2019 |
07/10/2019 |
08/01/2019 |
| |
| 004 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 024) T. 314.16 A DEVICE BOX(S) TOO SMALL |
RSLV |
07/10/2019 |
07/10/2019 |
08/01/2019 |
| |
| 005 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 024)110.2,3,7 OPEN WIRING IN ACCESS DOOR FOR LED DRIVER |
RSLV |
07/10/2019 |
07/10/2019 |
08/01/2019 |
| |
| 006 |
( 11) |
FEEDER CONDUCTORS ARE NOT OF PROPER SIZE (ALL FLOORS)T. 310.16, 240.4 350 MCM CONDUCTORS ON 350 A CB |
RSLV |
07/10/2019 |
07/10/2019 |
08/09/2019 |