BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z161015
Premises: 246 WEST 108 STREET MANHATTAN BIN: 1056669     Block: 1879   Lot: 56
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 246 W 108 ST Census Tract:   195 Health Area:  2310
CELLAR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   AMSTERDAM AVENUE,    BROADWAY
Status:   C - JOB IS SIGNED OFF 01/30/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/05/2017 9:57 AM
Application Entered:   06/05/2017 Job Start Date:   06/05/2017
Last Change:   01/30/2019 Job End Date:   06/01/2018
Appointment Status:   
Last Inspection By:   VINCENT CASTALDO       On     01/08/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012057 Licensee Name: MIKHAIL LEYBMAN
Firm: 003746 Firm Name: RELIABLE ELEC'L CONTR'S
Firm Phone: 347-987-3221  Firm Address: 167 7TH STREET INC BROOKLYN NY 11215 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $523.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID MOORE
Owner Business Name: 246 WEST 108TH STREET LLC
Authorized Representative:  DAVID MOORE
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  11  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  11  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 11 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/05/2017 Notice: 1 - FIRST NOTICE 06/22/2018
Power Issued: 06/05/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW ELECTRICAL SERVICE INSTALLATION

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z161015
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/22/2018 06/22/2018 AYC V (84) (4)
INSPECTION COMMENTS: FAIL. 11 FEEDERS ONLY PROVIDED TO THE LINE SIDE OF THE ELECTRICAL METERS.
 
(2) 01/08/2019 01/08/2019 VTC C R (70) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: Z161015
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (123) SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED
(BASEMENT) SERVICE SWITCH NOT IDENTIFIED. ART. 110.3
RSLV 06/22/2018 06/22/2018 01/08/2019
 
002 (134) GROUNDING CONNECTION IS NOT WITHIN 5FT
(BASEMENT)SERVICE GROUND NOT INSTALLED WITHIN 5 FEET OF WATER LINE ENTRY OFPROPERTY. ART. 250.52
RSLV 06/22/2018 06/22/2018 01/08/2019
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) SERVICE SWITCH MISSING ARC FLASH LABEL. ART. 110.16
RSLV 06/22/2018 06/22/2018 01/08/2019
 
004 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT)SERVICE ENTRANCE CONDUCTORS ARE NOT ENCASED IN CONCRETE. ART. 230.6
RSLV 06/22/2018 06/22/2018 01/08/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order