Electrical Application Details for App #: Z160965
Premises: 115 CENTRAL PARK WEST MANHATTAN BIN: 1028618     Block: 1124   Lot: 27
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 115 CENTRAL PARK W Census Tract:   157 Health Area:  4000
15 E, 16E Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   WEST 71 STREET,    CENTRAL PARK EXIT WEST 72 ST
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/01/2017 12:34 PM
Application Entered:   06/01/2017 Job Start Date:   06/01/2017
Last Change:   08/22/2025 Job End Date:   06/01/2018
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     08/31/2018      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 010983 Licensee Name: JOSEPH J SGROI
Firm: 000794 Firm Name: JOSEPH SGROI & SONS, INC.
Firm Phone: 718-728-3510  Firm Address: 34-06 44TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $131.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MIKE CITAK
Authorized Representative:  MIKE CITAK
Relationship To Owner:   GENERAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  42 CIRCUIT 200 AMP
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
015  15 E    15             
016  16E  58  45  30  58  10         
Buildings Total 58  60  32  58     15           
Total Units : 227 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 08/29/2018
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z160965
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/28/2018 08/29/2018 PHG V (60) (2)
INSPECTION COMMENTS: CHANGES MADE TO APP
 
(2) 08/31/2018 08/31/2018 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000013664

OBJECTION FOR APPLICATION #: Z160965
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 015) LOAD CALCULATION NEEDED 60 AMP FEED PANEL 220.40
OPEN 08/28/2018 08/28/2018
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 016) 2 WIRES UNDER 1 LUG PANEL FEEDER 110.3
RSLV 08/28/2018 08/28/2018 08/31/2018