BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z160858
Premises: 12 WEST 72 STREET MANHATTAN BIN: 1028619     Block: 1124   Lot: 42
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 12 W 72ND ST Census Tract:   157 Health Area:  4000
CLR & 1ST FLOOR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
Special Place Name:   WCMC PRIVATE PRACTICE
DOB Cross Street(s):   CENTRAL PARK EXIT WEST 72 ST,    COLUMBUS AVENUE
Status:   C - JOB IS SIGNED OFF 03/05/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/24/2017 2:09 PM
Application Entered:   05/24/2017 Job Start Date:   05/26/2017
Last Change:   03/05/2020 Job End Date:   05/31/2018
Appointment Status:   
Last Inspection By:   VINCENT CASTALDO       On     03/05/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010487 Licensee Name: CIRO LUPO
Firm: 001787 Firm Name: COMMERCIAL ELECT CONT INC
Firm Phone: 718-784-3500  Firm Address: 10-28 47TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $357.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: OLIVER CROMWELL OWNERS LL
Authorized Representative:  ALREDO SALSANO
Relationship To Owner:   BLDG PRESIDENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  (4) SETS #4
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  1001 MCB 120/208V 10KAIC
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    20  65    23  58             
001    40  150    60  102             
Buildings Total 60  215    83  160                
Total Units : 518 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/04/2020
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WCMC PRIVATE PRACTICE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z160858
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/25/2019 09/25/2019 GYM V (85) (6)
INSPECTION COMMENTS: FULL INSPECTION REQUIRED.
 
(2) 02/03/2020 02/04/2020 VTC V Y (60) (2)
INSPECTION COMMENTS: FAIL- SEE LIST
 
(3) 03/05/2020 03/05/2020 VTC C R (45) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: Z160858
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 29) OUTLET BOXES ARE NOT COVERED
(BASEMENT) OPEN BOXES THRU OUT
RSLV 09/25/2019 09/25/2019 03/05/2020
 
002 ( 30) OUTLET BOXES ARE NOT SECURED
(BASEMENT) OUTLET BOXES THRU OUT
RSLV 09/25/2019 09/25/2019 03/05/2020
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(BASEMENT) PANELS
RSLV 09/25/2019 09/25/2019 03/05/2020
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
(BASEMENT) PANTRY
RSLV 09/25/2019 09/25/2019 03/05/2020
 
005 (999) OTHER
(BASEMENT) FEEDERS DIAGRAM REQUIRED 215.5
RSLV 09/25/2019 09/25/2019 02/03/2020
 
006 (999) OTHER
(BASEMENT)MC CABLE USED EXAM ROOMS 517.13 (BASEMENT & GROUND FLOORS)
RSLV 09/25/2019 09/25/2019 02/03/2020
 
007 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
(ALL FLOORS)LIGHT FIXTURES IN SUSPENDED CEILINGS NOT PROPERLY SUPPORTED 410.36B
RSLV 02/03/2020 02/03/2020 03/05/2020
 
008 ( 53) GFCI HAS NOT BEEN PROVIDED
(BASEMENT)GFCI MISSING IN BATHROOMS AND WITHIN 6 FEET OF SINKS 210.8
RSLV 02/03/2020 02/03/2020 03/05/2020