BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z160142
Premises: 1012 RIVERSIDE DRIVE MANHATTAN BIN: 1076746     Block: 2139   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 177 FORT WASHINGTON AV Census Tract:   255 Health Area:  8700
8TH. FLOOR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   A
NEW YORK, NY 10032 Community Board:   112
Special Place Name:   NEW YORK PRESBYTERIAN HOSPITAL
DOB Cross Street(s):   WEST 165 STREET,    WEST 168 STREET
Status:   C - JOB IS SIGNED OFF 04/10/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/12/2017 8:17 AM
Application Entered:   04/12/2017 Job Start Date:   04/12/2017
Last Change:   04/10/2018 Job End Date:   04/12/2020
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     04/09/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009886 Licensee Name: ROBERT A HEMSING
Firm: 000440 Firm Name: DOOLEY ELECTRIC CO., INC.
Firm Phone: 718-840-2200  Firm Address: 4014 3RD AVENUE BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $854.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: NY PRESBYTERIAN HOSPITAL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  6  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  6  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
008    200  414    170  415          150 
Buildings Total 200  414    170  415               150 
Total Units : 1349 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/29/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  #31619 NYPH - MILSTEIN BED UNIT 8-HUDSON SOUTH

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z160142
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/28/2018 03/29/2018 MQY V (90) (1)
INSPECTION COMMENTS: ISSUED OBJECTION ON TRANSFORMER GROUNDING ELECTRODE CONDUCTOR AND DERIVED SIDE GROUNDING CONDUCTOR
 
(2) 04/09/2018 04/10/2018 GYM C R (55) (0)
INSPECTION COMMENTS: OBJECTION REMOVED.

OBJECTION FOR APPLICATION #: Z160142
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 008)GROUNDING ELECTRODE CONDUCTOR UNDERSIZED @ COLLECTIVE BAR &SECONDARY DISCONNECT (250.66)
RSLV 03/28/2018 03/28/2018 04/09/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order