BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z160059
Premises: 35 FT WASHINGTON AVENUE MANHATTAN BIN: 1063321     Block: 2136   Lot: 83
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 35 FORT WASHINGTON AV Census Tract:   247 Health Area:  0500
6D Admin Area:   Z - UPPER MANHATTAN Inspection Area:   B
NEW YORK, NY 10032 Community Board:   112
DOB Cross Street(s):   WEST 160 STREET,    WEST 161 STREET
Status:   C - JOB IS SIGNED OFF 11/03/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/06/2017 10:55 PM
Application Entered:   04/06/2017 Job Start Date:   04/07/2017
Last Change:   11/03/2017 Job End Date:   12/13/2017
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     11/03/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012202 Licensee Name: LUIS LINARES
Firm: 003915 Firm Name: ECO ELECTRICAL CORP
Firm Phone: 347-590-8077  Firm Address: 714 EAST 180TH STREET BRONX NY 10457 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $106.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT J MEJIA
Owner Business Name: ROSMIL TILE & PAINTING CO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  20/24 SPACE PANEL
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
006                         
006  6D  39  32  13  39             
Buildings Total 39  32  13  39                
Total Units : 127 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/19/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z160059
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/01/2017 08/01/2017 UMS V (15) (1)
INSPECTION COMMENTS: CONTRACTOR REFUSED TO CONTINUE WITH THE INSPECTION AFTER FINDING OUT THAT THE JOB WAS NOT GOING TO PASS. FULL INSPECTION NEEDED
 
(2) 09/12/2017 09/13/2017 GYM V X (60) (3)
INSPECTION COMMENTS: ISSUED OBJECTION FINAL.
 
(3) 10/18/2017 10/19/2017 MQY V R (45) (2)
INSPECTION COMMENTS: RESOLVED OBJECTIONS. COMPUTER FROZE AND MY START TIME DISAPPEARED. 5:35PM START TIME MAY HAVE BEEN 5-10 MIN LATER
 
(4) 11/03/2017 11/03/2017 EDB C R (65) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: Z160059
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 006) RECEPTACLES NEED TO BE OF THE TR TYPE. NEC 406
RSLV 08/01/2017 08/01/2017 10/18/2017
 
002 (999) OTHER
(FLOOR: 006) KITCHEN MIN 2 20 AMP CIRCUITS REQ'D 210.11
RSLV 09/12/2017 09/12/2017 10/18/2017
 
003 (999) OTHER
(FLOOR: 006) KITCHEN COUNTERTOP MISSING RECEPTACLE 210.52
RSLV 09/12/2017 09/12/2017 10/18/2017
 
004 (999) OTHER
(FLOOR: 006) OUTLET BOXES BONDING JUMPER 110.2
RSLV 09/12/2017 09/12/2017 10/18/2017
 
005 (999) OTHER
(FLOOR: 006)MICROWAVE RECEPTACLE SETBACK ON WOOD WITHOUT PROTECTION (314.20)
RSLV 10/18/2017 10/18/2017 11/03/2017
 
006 (999) OTHER
(FLOOR: 006) FRONT ENTRY CLOSET; OPEN INCANDESCENT BULB (410.16)
RSLV 10/18/2017 10/18/2017 11/03/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.