Premises: 465 CENTRAL PARK WEST MANHATTAN BIN: 1055659     Block: 1842   Lot: 32
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 465 CENTRAL PARK W Census Tract:   193 Health Area:  2320
BASEMENT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   CENTRAL PARK ENTRANCE W 106 ST,    WEST 107 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/02/2017 5:20 PM
Application Entered:   03/02/2017 Job Start Date:   03/03/2017
Last Change:   08/22/2025 Job End Date:   03/01/2018
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     10/06/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 012216 Licensee Name: LARRY M ZASSMAN
Firm: 004467 Firm Name: VILLAGE ELECTL CONTRS INC
Firm Phone: 917-305-9050  Firm Address: 128-10 111TH STREET SOUTH OZONE PARK NY 11420 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $595.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   H - Hotel
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT VIALTA
Owner Business Name: ERICA LEE CORP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  4  4 SETS 500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 03/02/2017 Notice: 1 - FIRST NOTICE 10/06/2017
Power Issued: 03/02/2017 Response:  

Follow-Up:
Contractor's Comments:  SUPERSEDING Z082716 AND Z130921

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z159505
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/05/2017 06/05/2017 MLF N (34) (0) Y
INSPECTION COMMENTS: .CONTRACTOR STATED THAT INSPECTION WAS CANCELLED
 
(2) 08/07/2017 08/07/2017 HRB N (30) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR THEY HAD NO IDEA THAT THEY HAS AN APPARENT THIS MORNING
 
(3) 09/19/2017 09/20/2017 MQY V (128) (4)
INSPECTION COMMENTS: CONTRACTOR FILED TO CLAIM 800A SERVICE SWITCH AND GROUND AND BOND IT
 
(4) 10/06/2017 10/06/2017 GYM V Y (80) (4)
INSPECTION COMMENTS: OLD CODE 4/1/2000

OBJECTION FOR APPLICATION #: Z159505
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT)SERVICE ENTRANCE CONDUCTORS UNDERSIZED. PARALLEL SET OF 500 MCM.ONE SET OF 500MCM IS NOT CONNECTED IN ENDLINE BOX SERVICE SWITCHFUSED @800A (230.42)
RSLV 09/19/2017 09/19/2017 10/06/2017
 
002 (999) OTHER
(BASEMENT) MAIN BONDING JUMPER MISSING FROM 800A SS (250.92)
OPEN 09/19/2017 09/19/2017
 
003 (999) OTHER
(BASEMENT)GROUNDING ELECTRODE CONDUCTOR SUBJECTED TO PHYSICAL DAMAGE (358.12)
RSLV 09/19/2017 09/19/2017 10/06/2017
 
004 (999) OTHER
(BASEMENT) SUPPLEMENTAL GROUND NOT TERMINATED (250.52)
OPEN 09/19/2017 09/19/2017
 
005 (999) OTHER
(BASEMENT) SERVICE SWITCHES IS NOT AS PER ART 27-3044
OPEN 10/06/2017 10/06/2017
 
006 (999) OTHER
(BASEMENT) SERVICE ENTRANCE CONDUCTOR IS NOT AS PER ART. 27-3044
OPEN 10/06/2017 10/06/2017
 
007 (999) OTHER
(BASEMENT) FIRE PUMP SERVICE IS NOT AS PER ART. 27-3109
OPEN 10/06/2017 10/06/2017
 
008 (999) OTHER
(BASEMENT) FIRE PUMP SERVICE SW. IS NOT AS PER ART. 27.3041
OPEN 10/06/2017 10/06/2017