BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z158797
Premises: 245 WEST 107 STREET MANHATTAN BIN: 1056647     Block: 1879   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 245 W 107TH ST Census Tract:   195 Health Area:  2310
APARTMENT 4E Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   AMSTERDAM AVENUE,    BROADWAY
Status:   C - JOB IS SIGNED OFF 10/23/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/16/2017 8:04 AM
Application Entered:   01/16/2017 Job Start Date:   01/17/2017
Last Change:   10/23/2025 Job End Date:   06/18/2017
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     08/21/2025      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012458 Licensee Name: FERGUS PLUNKETT
Firm: 003307 Firm Name: CAVAN ELECTRIC CORP.
Firm Phone: 718-779-7259  Firm Address: 48-08 70TH STREET WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $62.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHRIS DUNN
Owner Business Name: 107 WEST APARTMENT CORP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004  4E  25  28    20  25             
Buildings Total 25  28    20  25                
Total Units : 98 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/30/2025
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z158797
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/29/2025 07/30/2025 MJK V (45) (1)
INSPECTION COMMENTS: COMPLETE. OBJECTION ISSUED. ATOI FERGUS AND WOJTEK
 
(2) 08/21/2025 08/21/2025 TSO C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-25-000035894

OBJECTION FOR APPLICATION #: Z158797
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)PAA TO FILE NEW APP FOR MISSING PANEL SINGLE PHASE 125A THAT WAS NOTFILED ON APP# Z158797
RSLV 07/29/2025 07/29/2025 08/21/2025



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order