Electrical Application Details for App #: Z158769
Premises: 2 RIVERSIDE BOULEVARD MANHATTAN BIN: 1089741     Block: 1171   Lot: 155
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 2 RIVERSIDE BLVD Census Tract:   151 Health Area:  3900
GROUND Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10069 Community Board:   107
Related Job Number:    121192976
DOB Cross Street(s):   WEST 59 STREET,    WEST 61 STREET
Status:   C - JOB IS SIGNED OFF 09/29/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/13/2017 8:18 AM
Application Entered:   01/13/2017 Job Start Date:   01/17/2017
Last Change:   09/29/2020 Job End Date:   12/30/2019
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     09/29/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012512 Licensee Name: WARREN BUBAK
Firm: 003078 Firm Name: KNIGHT ELEC'L SERV. CORP.
Firm Phone: 212-989-2333  Firm Address: 599 11TH AVENUE, 7TH FLOOR NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $1,414.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANDREW EDWARDS
Owner Business Name: TISHMAN CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  9  
B. Each Additional 10 Floors Or Less  3  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/25/2020
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z158769
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/28/2020 08/31/2020 MJD V (90) (5)
INSPECTION COMMENTS: FAIL. INSPECTION COMPLETE
 
(2) 09/24/2020 09/25/2020 CDX V R (45) (1)
INSPECTION COMMENTS: FAIL. COMPLETE INSPECTION. OBJECTION ISSUED.
 
(3) 09/29/2020 09/29/2020 TSO C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-20-000022209

OBJECTION FOR APPLICATION #: Z158769
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (271) BONDING INSUFFICIENT, OVER 250 VOLTS
(FLOOR: 029) 250.97 ELEVATOR DISCONNECT B4 MISSING GROUNDING BUSHING
RSLV 08/28/2020 08/28/2020 09/24/2020
 
002 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(FLOOR: 029) 110.12(A) CAB LIGHT B4 MISSING KO
RSLV 08/28/2020 08/28/2020 09/24/2020
 
003 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ALL FLOORS) 250.122 EGC IS UNDERSIZED FOR ALL CAB LIGHT DISCONNECTS
RSLV 08/28/2020 08/28/2020 09/24/2020
 
004 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)110.14(A) GROUND CONDUCTORS DOUBLE LOGGED IN ALL CAR LIGHT SWITCHES
RSLV 08/28/2020 08/28/2020 09/24/2020
 
005 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(CELLAR) 620.24 PIT D1 HAS A FAULTY GFCI RECEPTACLE
RSLV 08/28/2020 08/28/2020 09/24/2020
 
006 (308) CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED
(FLOOR: 024)110.14 - 110.3(B)- AM 110.2(A) EGC DOUBLE LUGGING TERMINATION ( CARLIGHT DISC SW ELEVATOR B4)
RSLV 09/24/2020 09/24/2020 09/29/2020



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.