BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z158452
Premises: 967 COLUMBUS AVENUE MANHATTAN BIN: 1055678     Block: 1843   Lot: 4
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 967 COLUMBUS AVE. Census Tract:   193 Health Area:  2320
APT 10, SUPER'S WORKSHOP Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10025 Community Board:   107
Related Job Number:    122831301
DOB Cross Street(s):   WEST 107 STREET,    WEST 108 STREET
Status:   C - JOB IS SIGNED OFF 03/08/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/19/2016 11:56 AM
Application Entered:   12/19/2016 Job Start Date:   12/19/2016
Last Change:   03/08/2017 Job End Date:   01/19/2017
Appointment Status:   
Last Inspection By:   MICHAEL QUERY       On     03/06/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009113 Licensee Name: MARTIN WEINSTEIN
Firm: 000796 Firm Name: JOSEPH WEINSTEIN ELECTRIC
Firm Phone: 718-843-5555  Firm Address: 94-24 88TH STREET CORP OZONE PARK NY 11416 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $160.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: STEVENSAM 967 REALTY LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  3 SETS OF #2AWG. 1 #2 TO
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL  WKSHP  14               
CEL  10  12  16    12             
001  10  12  16    12             
Buildings Total 32  46    20  32                
Total Units : 130 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/10/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  THIS APPLICATION SUPERSEDES APPLICATION NO. A158007 FOR THEPURPOSE OF CORRECTING FLOOR INFORMATION.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z158452
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/08/2017 02/10/2017 BUR V (55) (3)
INSPECTION COMMENTS: RE Z158007
 
(2) 03/06/2017 03/06/2017 MQY C R (46) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED. FEEDERS ADDED

OBJECTION FOR APPLICATION #: Z158452
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT)APT 10A RISER NOT MAKING MECHANICAL CONNECTION TO METER BANKPROPERLY 250.12
RSLV 02/08/2017 02/08/2017 03/06/2017
 
002 (999) OTHER
(CELLAR) RISER TAPPED MORE THAN 25 FEET WITH OCP PROTECTION 240.21
RSLV 02/08/2017 02/08/2017 03/06/2017
 
003 (999) OTHER
(CELLAR)SUPER WORK ROOM RISER NOT CONNECTED PROPERLY TO JUNCTION BOX 250.8
RSLV 02/08/2017 02/08/2017 03/06/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.