Electrical Application Details for App #: Z158286
Premises: 180 CABRINI BOULEVARD MANHATTAN BIN: 1079988     Block: 2179   Lot: 10
   

DOB NOW: Inspections


Filed: 180 CABRINI BLVD Census Tract:   275 Health Area:  8700
APT 82 Admin Area:   Z - UPPER MANHATTAN Inspection Area:   A
NEW YORK, NY 10033 Community Board:   112
DOB Cross Street(s):   WEST 181 STREET,    WEST 186 STREET
Status:   K - CLOSED/CANCELLED 05/13/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/07/2016 1:38 PM
Application Entered:   12/07/2016 Job Start Date:   12/07/2016
Last Change:   05/13/2020 Job End Date:   12/07/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     05/13/2020      
Field Disp:   K - OK TO CANCEL
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012393 Licensee Name: MICHAEL R MATTEI
Firm: 004186 Firm Name: H.P. ELVTR AND ELCTL SVCS
Firm Phone: 718-761-3979  Firm Address: 780 GULF AVENUE INC STATEN ISLAND NY 10314 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $53.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: STEPHEN TOCCO
Owner Business Name: CASTLE VILLAGE OWNERS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  40 AMP USING 3 # 8 WIRES
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
082  16               
Buildings Total 16                  
Total Units : 33 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/22/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z158286
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/14/2017 12/15/2017 DNM N (15) (0) Y
INSPECTION COMMENTS: WAITED WITH CONTRACTOR, NO ACCESS.
 
(2) 01/03/2018 01/03/2018 GYM V (55) (8)
INSPECTION COMMENTS: FAIL
 
(3) 07/19/2019 07/22/2019 RDY V R (55) (2)
INSPECTION COMMENTS: INSPECTION FAILED. CONTRACTOR HAD 8 OBJECTIONS HE REMOVED 8 OBJECTIONS I ADDED 2 OBJECTIONS. INSPECTED APARTMENT NUMBER 81.INSPECTED LEFT SIDE OF APARTMENT.
 
(4) 05/13/2020 05/13/2020 TUR K R (1) (0)
INSPECTION COMMENTS: SEE REQ COMMENT

OBJECTION FOR APPLICATION #: Z158286
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 008) NEW PANEL
RSLV 01/03/2018 01/03/2018 07/19/2019
 
002 (999) OTHER
(FLOOR: 008) BATH ROOM GFCI REQUIRED 210.8
RSLV 01/03/2018 01/03/2018 07/19/2019
 
003 (999) OTHER
(FLOOR: 008) AFCI REQUIRED ALL ROOMS 210.12
RSLV 01/03/2018 01/03/2018 07/19/2019
 
004 (999) OTHER
(FLOOR: 008) CONDUCTORS FILL EXCEEDS RACEWAY 300.17
RSLV 01/03/2018 01/03/2018 07/19/2019
 
005 (999) OTHER
(FLOOR: 008) AC RECEPTACLES BED ROOM & LIVING ROOM DEFECTIVE 110.2
RSLV 01/03/2018 01/03/2018 07/19/2019
 
006 (999) OTHER
(FLOOR: 008) DEDICATED 20 AMP CIRCUIT TO EACH AC RECEPTACLE 210.11
RSLV 01/03/2018 01/03/2018 07/19/2019
 
007 (999) OTHER
(FLOOR: 008) SPLICE BOXES MUST REMAIN ACCESSIBLE 314.29
RSLV 01/03/2018 01/03/2018 07/19/2019
 
008 (999) OTHER
(FLOOR: 008) OUTLET BOXES MISSING BONDING JUMPERS 250.146
RSLV 01/03/2018 01/03/2018 07/19/2019
 
009 (999) OTHER
(FLOOR: 008)CONTRACTOR NEEDS TO REFILE TO ADD 125 AMP PANEL AND NUMBER 8FEEDERS.
RSLV 07/19/2019 07/19/2019 05/13/2020
 
010 (999) OTHER
(FLOOR: 008)CONTRACTOR HAS AN OPEN GROUND ON RECEPTACLE IN TV ROOM. 250.118
RSLV 07/19/2019 07/19/2019 05/13/2020