| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
40 AMP USING 3 # 8 WIRES |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 008) NEW PANEL |
RSLV |
01/03/2018 |
01/03/2018 |
07/19/2019 |
| |
| 002 |
(999) |
OTHER (FLOOR: 008) BATH ROOM GFCI REQUIRED 210.8 |
RSLV |
01/03/2018 |
01/03/2018 |
07/19/2019 |
| |
| 003 |
(999) |
OTHER (FLOOR: 008) AFCI REQUIRED ALL ROOMS 210.12 |
RSLV |
01/03/2018 |
01/03/2018 |
07/19/2019 |
| |
| 004 |
(999) |
OTHER (FLOOR: 008) CONDUCTORS FILL EXCEEDS RACEWAY 300.17 |
RSLV |
01/03/2018 |
01/03/2018 |
07/19/2019 |
| |
| 005 |
(999) |
OTHER (FLOOR: 008) AC RECEPTACLES BED ROOM & LIVING ROOM DEFECTIVE 110.2 |
RSLV |
01/03/2018 |
01/03/2018 |
07/19/2019 |
| |
| 006 |
(999) |
OTHER (FLOOR: 008) DEDICATED 20 AMP CIRCUIT TO EACH AC RECEPTACLE 210.11 |
RSLV |
01/03/2018 |
01/03/2018 |
07/19/2019 |
| |
| 007 |
(999) |
OTHER (FLOOR: 008) SPLICE BOXES MUST REMAIN ACCESSIBLE 314.29 |
RSLV |
01/03/2018 |
01/03/2018 |
07/19/2019 |
| |
| 008 |
(999) |
OTHER (FLOOR: 008) OUTLET BOXES MISSING BONDING JUMPERS 250.146 |
RSLV |
01/03/2018 |
01/03/2018 |
07/19/2019 |
| |
| 009 |
(999) |
OTHER (FLOOR: 008)CONTRACTOR NEEDS TO REFILE TO ADD 125 AMP PANEL AND NUMBER 8FEEDERS. |
RSLV |
07/19/2019 |
07/19/2019 |
05/13/2020 |
| |
| 010 |
(999) |
OTHER (FLOOR: 008)CONTRACTOR HAS AN OPEN GROUND ON RECEPTACLE IN TV ROOM. 250.118 |
RSLV |
07/19/2019 |
07/19/2019 |
05/13/2020 |