| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
60 AMP SERVICE SW. |
| B. 101 Up to 200 AMPS |
1 |
200AMP |
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
1 |
1 1200 AMP SERVICE SW. |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
1 |
SET OF(4) #6'S |
| C. Over 1/0 to 250 MCM |
2 |
1-SET(4)#3/0'S&1-SET(4)25 |
| D. Over 250 MCM |
3 |
SERVICE CONDUCTORS |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
60AMP |
| D. 3 Phase Over 225 AMPS |
1 |
1200AMP |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (BASEMENT) SERVICE SWITCH 6 SERVICE RACEWAY NOT BONDED (250.92) |
RSLV |
08/23/2017 |
08/23/2017 |
02/08/2018 |
| |
| 002 |
(999) |
OTHER (BASEMENT) FUSES DONT MATCH T-OUT FUSE TYPES (110.12) |
RSLV |
08/23/2017 |
08/23/2017 |
02/08/2018 |
| |
| 003 |
(999) |
OTHER (BASEMENT) SERVICE SWITCH 6 GEC NOT AS PER 250.66 |
RSLV |
08/23/2017 |
08/23/2017 |
11/27/2017 |
| |
| 004 |
(999) |
OTHER (BASEMENT) SS6 NEED TO BE IDENTIFIED AS SERVICE SWITCH |
RSLV |
08/23/2017 |
08/23/2017 |
02/08/2018 |
| |
| 005 |
(999) |
OTHER (BASEMENT)SUPPLEMENTAL GROUND NOT PROVIDED AS PER PLANS T-OUT(110.12) |
RSLV |
08/23/2017 |
08/23/2017 |
11/27/2017 |
| |
| 006 |
(999) |
OTHER (BASEMENT)EXISTING GEC RACEWAY NOT CONTINUOUS (POKE THROUGH INSIDE EQUIPMENT)250.64 |
RSLV |
08/23/2017 |
08/23/2017 |
02/08/2018 |
| |
| 007 |
(999) |
OTHER (BASEMENT)SERVICE CONDUCTORS AND FEEDERS IN THE SAME RACEWAY WIREWAY IN THEBACK OF THE SERVICE EQUIPMENT (230.7) |
RSLV |
08/23/2017 |
08/23/2017 |
02/08/2018 |
| |
| 008 |
(999) |
OTHER (BASEMENT) ARC FLASH WARNING LABEL REQ. 110.16 |
RSLV |
11/27/2017 |
11/27/2017 |
02/08/2018 |
| |
| 009 |
(999) |
OTHER (BASEMENT) NEW PANEL MULTI WIRES REQ. HANDLE TIE 210.4 |
RSLV |
11/27/2017 |
11/27/2017 |
02/08/2018 |
| |
| 010 |
(999) |
OTHER (BASEMENT) WATER METER JUMPER UNDER SIZE 250.66 |
RSLV |
11/27/2017 |
11/27/2017 |
02/08/2018 |
| |
| 011 |
(999) |
OTHER (BASEMENT) NEW PANEL GREEN WIRE USED AS PHASE 110.2 |
RSLV |
11/27/2017 |
11/27/2017 |
02/08/2018 |
| |
| 012 |
(999) |
OTHER (BASEMENT)EACH SERVICE DISC. MEANS SHALL BE PERMANENTLY MARKED 230.70 |
RSLV |
11/27/2017 |
11/27/2017 |
02/08/2018 |
| |
| 013 |
(999) |
OTHER (BASEMENT)NO GROUNDING ELECTRODE PROVIDED NEW 1200 AMP SERVICE SW. 250.66 |
RSLV |
11/27/2017 |
11/27/2017 |
02/08/2018 |
| |
| 014 |
(999) |
OTHER (BASEMENT)800 AMP FIRE PUMP SERVICE SW. REQ. 12" MINIMUM FROM SERVICE SW'S.695.4 |
RSLV |
11/27/2017 |
11/27/2017 |
02/08/2018 |
| |
| 015 |
(999) |
OTHER (BASEMENT) FIRE PUMP SERVICE SW. NOT MARKED DO NOT DISCONNECT 695.4 |
RSLV |
11/27/2017 |
11/27/2017 |
02/08/2018 |
| |
| 016 |
(999) |
OTHER (BASEMENT) DOORS PANIC HARDWARE PROVIDED 110.26 |
RSLV |
11/27/2017 |
11/27/2017 |
02/08/2018 |
| |
| 017 |
(999) |
OTHER (GROUND FLOOR)NO FEEDERS IN SAME RACEWAY WITH SERVICE CONDUCTORS 230.7 |
RSLV |
11/27/2017 |
11/27/2017 |
02/08/2018 |