BIS Menu  |  Comments  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z157621
Premises: 602 WEST 112 STREET MANHATTAN BIN: 1057331     Block: 1894   Lot: 56
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 610 W 112 ST Census Tract:   199
CELLAR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10025 Community Board:   109
Special Place Name:   BANK STREET COLLEGE OF EDUCATION
DOB Cross Street(s):   BROADWAY,    RIVERSIDE DRIVE
Status:   C - JOB IS SIGNED OFF 02/09/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   10/26/2016 Job Start Date:   10/01/2016
Last Change:   02/09/2018 Job End Date:   12/31/2017
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     02/08/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011766 Licensee Name: GARY BLANKOPH
Firm: 003683 Firm Name: COGEN ELEC'L SERVICES,INC
Firm Phone: 718-991-6999  Firm Address: 175 CITY ISLAND AVENUE BRONX NY 10464 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $773.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54085     Submittal #: 16A0498  
Owner / Occup:
Owner Business Name: BANK STREET COLLEGE OF ED
Authorized Representative:  JUSTIN TYACK
Relationship To Owner:   COO


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  60 AMP SERVICE SW.
B. 101 Up to 200 AMPS  1  200AMP
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  1 1200 AMP SERVICE SW.
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  SET OF(4) #6'S
C. Over 1/0 to 250 MCM  2  1-SET(4)#3/0'S&1-SET(4)25
D. Over 250 MCM  3  SERVICE CONDUCTORS
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  60AMP
D. 3 Phase Over 225 AMPS  1  1200AMP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/28/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z157621
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/04/2017 04/05/2017 UMS J (60) (0) Y
INSPECTION COMMENTS: DID NOT HAVE REVISION #2 WITH ME . FULL INSPECTION IS NEEDED
 
(2) 06/30/2017 06/30/2017 JUU J (45) (0) Y
INSPECTION COMMENTS: CONTRACTOR NEEDS TO FILE REV 2 TO ADVISORY BOARD
 
(3) 08/23/2017 08/23/2017 MQY V (88) (7)
INSPECTION COMMENTS: ISSUED OBJECTIONS. INSPECTED SERVICE ROOM
 
(4) 11/27/2017 11/28/2017 GYM V Y (150) (10)
INSPECTION COMMENTS: ADD 1, 1200 AMP 1, 60 AMP SERVICE SWITCHES, SERVICE CONDUCTORS, SEE APPL. #Z154976 NEED DRAWING FOR NEXT INSPECTION. (REV. # 2)
 
(5) 02/08/2018 02/09/2018 DNM C R (120) (0)
INSPECTION COMMENTS: JOB PASS, ALL OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: Z157621
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) SERVICE SWITCH 6 SERVICE RACEWAY NOT BONDED (250.92)
RSLV 08/23/2017 08/23/2017 02/08/2018
 
002 (999) OTHER
(BASEMENT) FUSES DONT MATCH T-OUT FUSE TYPES (110.12)
RSLV 08/23/2017 08/23/2017 02/08/2018
 
003 (999) OTHER
(BASEMENT) SERVICE SWITCH 6 GEC NOT AS PER 250.66
RSLV 08/23/2017 08/23/2017 11/27/2017
 
004 (999) OTHER
(BASEMENT) SS6 NEED TO BE IDENTIFIED AS SERVICE SWITCH
RSLV 08/23/2017 08/23/2017 02/08/2018
 
005 (999) OTHER
(BASEMENT)SUPPLEMENTAL GROUND NOT PROVIDED AS PER PLANS T-OUT(110.12)
RSLV 08/23/2017 08/23/2017 11/27/2017
 
006 (999) OTHER
(BASEMENT)EXISTING GEC RACEWAY NOT CONTINUOUS (POKE THROUGH INSIDE EQUIPMENT)250.64
RSLV 08/23/2017 08/23/2017 02/08/2018
 
007 (999) OTHER
(BASEMENT)SERVICE CONDUCTORS AND FEEDERS IN THE SAME RACEWAY WIREWAY IN THEBACK OF THE SERVICE EQUIPMENT (230.7)
RSLV 08/23/2017 08/23/2017 02/08/2018
 
008 (999) OTHER
(BASEMENT) ARC FLASH WARNING LABEL REQ. 110.16
RSLV 11/27/2017 11/27/2017 02/08/2018
 
009 (999) OTHER
(BASEMENT) NEW PANEL MULTI WIRES REQ. HANDLE TIE 210.4
RSLV 11/27/2017 11/27/2017 02/08/2018
 
010 (999) OTHER
(BASEMENT) WATER METER JUMPER UNDER SIZE 250.66
RSLV 11/27/2017 11/27/2017 02/08/2018
 
011 (999) OTHER
(BASEMENT) NEW PANEL GREEN WIRE USED AS PHASE 110.2
RSLV 11/27/2017 11/27/2017 02/08/2018
 
012 (999) OTHER
(BASEMENT)EACH SERVICE DISC. MEANS SHALL BE PERMANENTLY MARKED 230.70
RSLV 11/27/2017 11/27/2017 02/08/2018
 
013 (999) OTHER
(BASEMENT)NO GROUNDING ELECTRODE PROVIDED NEW 1200 AMP SERVICE SW. 250.66
RSLV 11/27/2017 11/27/2017 02/08/2018
 
014 (999) OTHER
(BASEMENT)800 AMP FIRE PUMP SERVICE SW. REQ. 12" MINIMUM FROM SERVICE SW'S.695.4
RSLV 11/27/2017 11/27/2017 02/08/2018
 
015 (999) OTHER
(BASEMENT) FIRE PUMP SERVICE SW. NOT MARKED DO NOT DISCONNECT 695.4
RSLV 11/27/2017 11/27/2017 02/08/2018
 
016 (999) OTHER
(BASEMENT) DOORS PANIC HARDWARE PROVIDED 110.26
RSLV 11/27/2017 11/27/2017 02/08/2018
 
017 (999) OTHER
(GROUND FLOOR)NO FEEDERS IN SAME RACEWAY WITH SERVICE CONDUCTORS 230.7
RSLV 11/27/2017 11/27/2017 02/08/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Comments  |  Electrical Inspection Work Order  |  Back