Electrical Application Details for App #: Z156994
Premises: 512 WEST END AVENUE MANHATTAN BIN: 1033124     Block: 1232   Lot: 61
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 514 W END AV Census Tract:   171 Health Area:  3400
16TH FLOOR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   WEST 84 STREET,    WEST 85 STREET
Status:   C - JOB IS SIGNED OFF 12/21/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/15/2016 12:17 PM
Application Entered:   09/15/2016 Job Start Date:   09/16/2016
Last Change:   12/21/2016 Job End Date:   05/15/2017
Appointment Status:   
Last Inspection By:   CHRISTOPHER PERDONCIN       On     11/17/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011903 Licensee Name: WIESLAW MAKSIM
Firm: 003541 Firm Name: DENMAR ELECTRIC CORP
Firm Phone: 718-533-6753  Firm Address: 5 PENN PLAZA 19TH FLOOR NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $176.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RICHARD EMERY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  2
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
016    62  72    33  62         
PEN                 
Buildings Total 67  80    35  67              
Total Units : 255 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/31/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z156994
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/28/2016 10/31/2016 UMS V (40) (7)
INSPECTION COMMENTS: JACUZZI MOTORS HAVE NOT BEEN INSPECTED. ACCESS DOOR TOO SMALL
 
(2) 11/17/2016 11/18/2016 CPP C R (41) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: Z156994
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 016) RECEPTACLES IN BATHROOMS NOT OF TR TYPE. NEC 406.11
RSLV 10/28/2016 10/28/2016 11/17/2016
 
002 (999) OTHER
(FLOOR: 016)RECEPTACLE IN BATHROOM CLOSE TO KITCHEN NOT GFI PROTECTED. NEC 210.8
RSLV 10/28/2016 10/28/2016 11/17/2016
 
003 (999) OTHER
(FLOOR: 016)EXPOSED INCANDESCENT LIGHT BULBS IN CLOTHES CLOSETS. NEC 410
RSLV 10/28/2016 10/28/2016 11/17/2016
 
004 (999) OTHER
(FLOOR: 016)NO HANDLE TIES PROVIDED FOR MULTIWIRE BRANCH CIRCUITS IN PANELS.NEC 210.4
RSLV 10/28/2016 10/28/2016 11/17/2016
 
005 (999) OTHER
(FLOOR: 016)NO ACCESS HAS BEEN PROVIDED TO JACUZZI MOTORS IN BOTH BATHROOMS.NEC 110.26
RSLV 10/28/2016 10/28/2016 11/17/2016
 
006 (999) OTHER
(FLOOR: 016)16 FL AND ROOF. OUTDOOR RECEPTACLES NOT OF TR TYPE. NEC 406.8
RSLV 10/28/2016 10/28/2016 11/17/2016
 
007 (999) OTHER
(ROOF)ROOF. A/C UNIT PLUS DISCONNECT SWITCH NOT GROUNDED. NEC 314.5 ,NEC 440.
RSLV 10/28/2016 10/28/2016 11/17/2016