Electrical Application Details for App #: Z156858
Premises: 405 CENTRAL PARK WEST MANHATTAN BIN: 1084008     Block: 1836   Lot: 29
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 405 CENTRAL PARK W Census Tract:   189 Health Area:  3210
STREET Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
Special Place Name:   DELI
DOB Cross Street(s):   CENTRAL PARK POOL PATH,    WEST 101 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/02/2016 11:44 PM
Application Entered:   09/02/2016 Job Start Date:   09/02/2016
Last Change:   08/22/2025 Job End Date:   09/02/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     11/24/2017      
Field Disp:   N - NO ACCESS
Energize Recommendation:  
Objection Disposition:  

License #: 012787 Licensee Name: SALADEEN ALCHAIB
Firm: 004640 Firm Name: APEX ELECTRIC CORP
Firm Phone: 718-680-6400  Firm Address: 44 MARJORIE ST SUITE D STATENISLAND NY 10309 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $226.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   DELI
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SADDEK ALSHABBI
Owner Business Name: PARK PLEASANT DELI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  1 SET 3/0 200 AMPS
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1 SET 3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  3P 200 A, 3P 100A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                   
GND    20  15             
Buildings Total 25  20                  
Total Units : 56 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 09/02/2016 Notice: 1 - FIRST NOTICE 10/06/2017
Power Issued: 09/02/2016 Response:  

Follow-Up:
Contractor's Comments:  SERVICE UPGRADE, AND GENERAL WIRING.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z156858
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/04/2017 10/06/2017 HRB V (55) (8)
INSPECTION COMMENTS: FAILED CONTRACTOR MUST AMEND OR REFILE APP TO SHOW FULL SCOPE OF WORK
 
(2) 11/24/2017 11/24/2017 MLF N (20) (0) Y
INSPECTION COMMENTS: NO ACCESS CALLED OFFICE " WILL RESCHEDULE"

OBJECTION FOR APPLICATION #: Z156858
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(BASEMENT) WRONG FUSE AND # 2 FUSED AT 225
OPEN 10/04/2017 10/04/2017
 
002 (279) WATER METER JUMPER IS MISSING/IMPROPER
(BASEMENT) METER JUMPER TO SMALL
OPEN 10/04/2017 10/04/2017
 
003 ( 29) OUTLET BOXES ARE NOT COVERED
(BASEMENT) OPEN BOX ABOVE HOT WATER TANK
OPEN 10/04/2017 10/04/2017
 
004 ( 37) MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED
(BASEMENT) NO SWITCH FOR HOT WATER TANK
OPEN 10/04/2017 10/04/2017
 
005 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
(BASEMENT) LIGHTS IN THE DROP CEILING NOT SUPPORTED
OPEN 10/04/2017 10/04/2017
 
006 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT)WATER GROUND AND GROUND ROD NOT GOING TO ALL SERVICE SWITCHES
OPEN 10/04/2017 10/04/2017
 
007 ( 53) GFCI HAS NOT BEEN PROVIDED
(BASEMENT) NEED GFI PROTECTION ALL OUTLETS IN BASEMENT
OPEN 10/04/2017 10/04/2017
 
008 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(OPEN SPACE) NO ACCESS TO OUTLET BELOW PANEL OUTSIDE COVER WONT OPEN
OPEN 10/04/2017 10/04/2017