Electrical Application Details for App #: Z156823
Premises: 301 WEST 75 STREET MANHATTAN BIN: 1031026     Block: 1185   Lot: 19
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 325 W END Census Tract:   163 Health Area:  3400
2C Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):       
Status:   C - JOB IS SIGNED OFF 04/11/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/01/2016 2:21 PM
Application Entered:   09/01/2016 Job Start Date:   09/01/2016
Last Change:   04/11/2017 Job End Date:   01/25/2017
Appointment Status:   
Last Inspection By:   MICHAEL QUERY       On     04/07/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011664 Licensee Name: BILLY B TRAN
Firm: 003220 Firm Name: BT ELECTRICAL, INC.
Firm Phone: 718-335-6697  Firm Address: 85-02 67TH DRIVE REGO PARK NY 11374 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $172.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ELIZABETH KEMPER-KONAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  3#1/0 THHN
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  2C  36  41  32  36             
Buildings Total 36  41  32  36                
Total Units : 149 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/01/2016 Notice: 1 - FIRST NOTICE 03/21/2017
Power Issued: 09/01/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z156823
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/20/2017 03/21/2017 MQY V (63) (5)
INSPECTION COMMENTS: ISSUED OBJECTION. CONTRACTOR CLAIMS IT IS ONLY A PARTIAL RENOVATION
 
(2) 04/07/2017 04/10/2017 MQY C R (65) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: Z156823
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 002)LIGHT ABOVE GUEST BATHROOM TUB NEEDS TO BE RATED FOR WET PURPOSE
RSLV 03/20/2017 03/20/2017 04/07/2017
 
002 (999) OTHER
(FLOOR: 002)AFCI PROTECTION NEEDED ON 110V A.C., MAIDS ROOM, AND OTHER REQUIREDCKTS (210.12)
RSLV 03/20/2017 03/20/2017 04/07/2017
 
003 (999) OTHER
(FLOOR: 002)OPENING FOR 1 OF THE KITCHEN LED DRIVER IS NOT ACCESSIBLE )(110.26)
RSLV 03/20/2017 03/20/2017 04/07/2017
 
004 (999) OTHER
(FLOOR: 002) DIRECTORY PROVIDED IS NOT ACCURATE (408.4)
RSLV 03/20/2017 03/20/2017 04/07/2017
 
005 (999) OTHER
(FLOOR: 002)NEUTRAL WIRE STRANDS CUT INSIDE THE 125AMP PANEL DISCONNECT IN THEBASEMENT (110.3)
RSLV 03/20/2017 03/20/2017 04/07/2017