Electrical Application Details for App #: Z156570
Premises: 48 WEST 73 STREET MANHATTAN BIN: 1028646     Block: 1125   Lot: 62
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 273 COLUMBUS AV Census Tract:   157 Health Area:  4000
BASEMENT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   WEST 72 STREET,    WEST 73 STREET
Status:   C - JOB IS SIGNED OFF 06/29/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/17/2016 8:30 AM
Application Entered:   08/17/2016 Job Start Date:   08/17/2016
Last Change:   06/29/2017 Job End Date:   10/30/2016
Appointment Status:   
Last Inspection By:   JOHN LAUNONEN       On     05/01/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011465 Licensee Name: LEONID ARLYUK
Firm: 002921 Firm Name: WTG ELECTRIC INC.
Firm Phone: 718-474-3400  Firm Address: 115-14 BEACH CHANNEL DRIVE ROCKAWAY PARK NY 11694 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $655.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (3  Stores, 36 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BISHOY TAKLA
Owner Business Name: BLDG MANAGEMENT CO
Authorized Representative:  BISHOY TAKLA
Relationship To Owner:   PROPERTY MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  3  4#500MCM AWG
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  3  3 SETS OF 500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  400A, 120/208VAC,3P,4W
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/17/2016 Notice: 1 - FIRST NOTICE 01/25/2017
Power Issued: 08/17/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  UPGRADING OF THE EXISTING ELECTRICAL SERVICE FOR THE NEW TENANT 'ZUCKER BAGEL'

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z156570
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/25/2017 01/25/2017 MQY V (64) (3)
INSPECTION COMMENTS: ISSUED OBJECTION
 
(2) 05/01/2017 05/01/2017 JUU C R (40) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: Z156570
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT)WHERE THE MAIN BONDING JUMPING IS A SCREW ONLY GROUNDING ELECTRODECONDUCTOR IS TO BE LANDED ON THE NEUTRAL (250.24)A4
RSLV 01/25/2017 01/25/2017 05/01/2017
 
002 (999) OTHER
(BASEMENT) GROUND ROD NOT PROVIDED (250.52)
RSLV 01/25/2017 01/25/2017 05/01/2017
 
003 (999) OTHER
(BASEMENT)KO SEAL NEEDED IN SS, TROUPH WAS PUT TOGETHER IN A MANNER THAT ATHERE IS A OPENING BIG ENOUGH FOR A HAND. (110.12)
RSLV 01/25/2017 01/25/2017 05/01/2017