BIS Menu  |  Elevators  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z156519
Premises: 74 PINEHURST AVENUE MANHATTAN BIN: 1064309     Block: 2177   Lot: 136
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 76 PINEHURST AV Census Tract:   265 Health Area:  0300
ROOF Admin Area:   Z - UPPER MANHATTAN Inspection Area:   A
NEW YORK, NY 10033 Community Board:   112
Special Place Name:   MANHATTAN
DOB Cross Street(s):   WEST 180 STREET,    WEST 181 STREET
Status:   C - JOB IS SIGNED OFF 02/08/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/12/2016 8:24 PM
Application Entered:   08/12/2016 Job Start Date:   08/12/2016
Last Change:   02/08/2017 Job End Date:   07/12/2017
Appointment Status:   
Last Inspection By:   JOFFRE PENA       On     01/20/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011316 Licensee Name: RALPH J RUSSO
Firm: 002733 Firm Name: RJ RUSSO ELECTRIC CO.
Firm Phone: 718-423-4742  Firm Address: 45-57 BELL BLVD BAYSIDE NY 11361 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
E - SUSTAINABLE ENERGY - SOLAR
Total Fee:  $128.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 74 PINEHURST AVE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  1-100 AMPS
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1 SET 4#2 WIRES,1-4#6
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1-125 AMPS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                      50 
ROF              73  23         
Buildings Total              23          50 
Total Units : 73 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/10/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SOLAR INSTALL,73 SOLAR MODULES 310 WATTS EACH,TOTAL 22,630 WATTS DC.1 INVERTER 3 PHASE,1 PANEL,1 TRANSFORMER,1 AC DISCONNECT,1 ARRAY ,2 STRINGS.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z156519
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/05/2017 01/10/2017 GYM V (60) (2)
INSPECTION COMMENTS: SOLAR, NO SERVICE INSTALLED.
 
(2) 01/20/2017 01/23/2017 JRP C R (35) (0)
INSPECTION COMMENTS: OBJECTION REMOVED. JOB COMPLETE

OBJECTION FOR APPLICATION #: Z156519
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) PANEL, DISC. SW. NEUTRAL BAR USED AS GROUND 250.24
RSLV 01/05/2017 01/05/2017 01/20/2017
 
002 (999) OTHER
(GROUND FLOOR) PANEL, DISC SW. NEUTRAL BOND NOT REQ. 250.24
RSLV 01/05/2017 01/05/2017 01/20/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.