BIS Menu  |  Elevators  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z156439
Premises: 369 EDGECOMBE AVENUE MANHATTAN BIN: 1061167     Block: 2054   Lot: 16
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 369 EDGECOMBE AV Census Tract:   235.01 Health Area:  0710
CELLAR;1 TO 5 FL.; ROOF Admin Area:   Z - UPPER MANHATTAN Inspection Area:   B
NEW YORK, NY 10031 Community Board:   109
Related Job Number:    121569613
DOB Cross Street(s):   WEST 150 STREET,    WEST 155 STREET
Status:   C - JOB IS SIGNED OFF 07/11/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/09/2016 5:39 AM
Application Entered:   08/09/2016 Job Start Date:   08/09/2016
Last Change:   07/11/2018 Job End Date:   08/08/2017
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     09/27/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012355 Licensee Name: PETER MILEVSKI
Firm: 003361 Firm Name: ELMAC ELECTRIC INC.
Firm Phone: 718-894-9727  Firm Address: 97-77 QUEENS BLVD TOWER FLOOR REGO PARK NY 11374 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $1,211.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: YVONNE STENNET
Owner Business Name: HEIGHTS 150 ST HDFC
Authorized Representative:  YVONNE STENNET
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  3PH; 100A
B. 101 Up to 200 AMPS  1  3 PH; 200A
C. 201 Up to 600 AMPS  1  3 PH; 600A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  16  3#6; 3#4
B. Over #2 to 1/0  1  4#1
C. Over 1/0 to 250 MCM  1  4#3/0
D. Over 250 MCM  2  4#350
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  16  24 CIRCUITS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  30 CIRCUITS; 42 CIRCUITS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  THERMOSTAT WIRING

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    24  30  14  35         
001    25  62  14  39             
002    28  68  16  28             
003    28  68  16  28             
004    28  68  16  28             
005    28  68  16  28             
ROF               
Buildings Total 164  365  41  92  189              
Total Units : 855 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 16 #4-Wire 2 #10-Wire 0
Existing Meters 17 + New Meters 18 - Removed Meters 17 = Total Meters 18

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/09/2016 Notice: 1 - FIRST NOTICE 08/21/2017
Power Issued: 08/09/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW WIRING FOR ENTIRE BUILDING; CLOSE ALL OPEN APPLICATIONS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z156439
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/21/2017 08/21/2017 UMS V (85) (1)
INSPECTION COMMENTS: SEE OBJECTION
 
(2) 09/27/2017 09/28/2017 EDB C R (95) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: Z156439
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT)COPPER DETAIL BOX FEEDING METERBANK RATED LESS THAN THE SERVICESWITCH AND ITS FUSED. ( 400 AMP COPPER DETAIL PROTECTED BY 600 AMPFUSES) NEC 110
RSLV 08/21/2017 08/21/2017 09/27/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elevators  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back