Electrical Application Details for App #: Z156176
Premises: 331 CENTRAL PARK WEST MANHATTAN BIN: 1031645     Block: 1207   Lot: 29
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 333 CENTRAL PARK W Census Tract:   177 Health Area:  3220
BASEMEN, 4TH FLR, APT. 44 Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   WEST 93 STREET,    WEST 94 STREET
Status:   C - JOB IS SIGNED OFF 01/19/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/19/2016 5:17 PM
Application Entered:   07/19/2016 Job Start Date:   07/19/2016
Last Change:   01/19/2017 Job End Date:   08/30/2016
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     01/17/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011465 Licensee Name: LEONID ARLYUK
Firm: 002921 Firm Name: WTG ELECTRIC INC.
Firm Phone: 718-474-3400  Firm Address: 115-14 BEACH CHANNEL DRIVE ROCKAWAY PARK NY 11694 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $124.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MORGAN HARTING
Authorized Representative:  MORGAN HARTING
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  3#1/0 AWG
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  200A,120/208V, 1PH,3W
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004  44  23  25    14    15         
Buildings Total 23  25    14       15           
Total Units : 77 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/19/2016 Notice: 1 - FIRST NOTICE 11/14/2016
Power Issued: 07/19/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  UPGRADING EXISTING ELECTRICAL POWER SUPPLY LINE TO THE APARTMENT 44 ON THE 4TH FLOOR

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z156176
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/14/2016 11/14/2016 UMS V (30) (3)
INSPECTION COMMENTS: SEE OBJECTIONS
 
(2) 01/17/2017 01/19/2017 BUR C R (35) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: Z156176
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 004) 120/208 VOLT DRYER REQUIRES NEUTRAL WIRE . NEC 110.3
RSLV 11/14/2016 11/14/2016 01/17/2017
 
002 (999) OTHER
(FLOOR: 004) LIVING ROOM RECEPTACLES NOT OF TR TYPE. NEC 406.11
RSLV 11/14/2016 11/14/2016 01/17/2017
 
003 (999) OTHER
(FLOOR: 004)LIVING ROOM RECEPTACLES NOT GROUNDED PROPERLY. NEC 250.146
RSLV 11/14/2016 11/14/2016 01/17/2017