BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z155908
Premises: 27 WEST 72 STREET MANHATTAN BIN: 1087511     Block: 1125   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 27 W 72 ST Census Tract:   157 Health Area:  4000
SIDEWALK Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   CENTRAL PARK EXIT WEST 72 ST,    COLUMBUS AVENUE
Status:   C - JOB IS SIGNED OFF 05/15/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/01/2016 6:42 AM
Application Entered:   07/01/2016 Job Start Date:   07/01/2016
Last Change:   05/15/2019 Job End Date:   07/01/2017
Appointment Status:   
Last Inspection By:   DHANESHWAR BISSOON       On     05/06/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010285 Licensee Name: GREGORY PAPANTONIOU
Firm: 003867 Firm Name: BOROWIDE ELECT'L CONTR'S
Firm Phone: 718-204-1347  Firm Address: 36-07 20TH AVENUE INC ASTORIA NY 11105 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
W - SIDEWALK SHED WIRING & LIGHTING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: JERRICK ASSOCIATES
Authorized Representative:  JIMMY DOWNES
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SWK                     
Buildings Total                     
Total Units : 4 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/11/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  TEMPORARY SHED LIGHTING WE ARE NOT RESPONSIBLE FOR FEED OR MAINTAINING LIGHTS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z155908
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/07/2017 12/11/2017 STP V (15) (3)
INSPECTION COMMENTS: FAIL. SHED STILL ACTIVE.
 
(2) 05/06/2019 05/06/2019 DWB C R (20) (0)
INSPECTION COMMENTS: MEET WITH SUPERINTENDENT OF THE BUILDING, SHED REMOVED.

OBJECTION FOR APPLICATION #: Z155908
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(GROUND FLOOR) LIGHT BOXS NEED SUPPORT 314.23
RSLV 12/07/2017 12/07/2017 05/06/2019
 
002 (999) OTHER
(GROUND FLOOR) SHED FED WITH ROMEX 334.12
RSLV 12/07/2017 12/07/2017 05/06/2019
 
003 (999) OTHER
(GROUND FLOOR) KO OPEN ON LIGHT BOX 110.12
RSLV 12/07/2017 12/07/2017 05/06/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back