BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z155759
Premises: 196 WEST 70 STREET MANHATTAN BIN: 1076231     Block: 1141   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 2025 BROADWAY Census Tract:   153 Health Area:  4000
APT 5 EF Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   WEST 69 STREET,    WEST 70 STREET
Status:   C - JOB IS SIGNED OFF 01/03/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/23/2016 7:15 AM
Application Entered:   06/23/2016 Job Start Date:   06/30/2016
Last Change:   01/03/2017 Job End Date:   10/30/2016
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     01/03/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010744 Licensee Name: ARTHUR DREYFUS
Firm: 003620 Firm Name: ILLUMINATIONS UNLMTD ELEC
Firm Phone: 212-228-2733  Firm Address: 439 LAFAYETTE STREET NEW YORK NY 10003 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $88.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RON SARILL
Owner Business Name: SR
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  1
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
005  EF  10  12    10  22             
Buildings Total 10  12    10  22                
Total Units : 54 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/18/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RENOVATION OF AN APT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z155759
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/17/2016 11/18/2016 UMS V (40) (5)
INSPECTION COMMENTS: NEW WIRING IN KITCHEN, LIVING ROOM, BABY'S ROOM AND BATHROOM. REST WAS EXISTING
 
(2) 12/01/2016 12/05/2016 BUR J Y (40) (0)
INSPECTION COMMENTS: SEE OBJECTION
 
(3) 01/03/2017 01/03/2017 BMP C R (35) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED. CERTIFIED.

OBJECTION FOR APPLICATION #: Z155759
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 005) RECEPTACLES NOT OF TR TYPE. NEC 406.11
RSLV 11/17/2016 11/17/2016 12/01/2016
 
002 (999) OTHER
(FLOOR: 005)NA HANDLE TIED HAVE BEEN PROVIDED FOR MULTI WIRE BRANCH CIRCUITS INNEW PANEL. NEC 210.4
RSLV 11/17/2016 11/17/2016 01/03/2017
 
003 (999) OTHER
(FLOOR: 005)NO AFCI PROTECTION HAS BEEN PROVIDED FOR 120 OUTLETS. NEC 210,12
RSLV 11/17/2016 11/17/2016 01/03/2017
 
004 (999) OTHER
(FLOOR: 005)RECEPTACLE OUTLETS IN LIVING ROOM NOT IN SUFFICIENT NUMBER. NEC210.52
RSLV 11/17/2016 11/17/2016 01/03/2017
 
005 (999) OTHER
(FLOOR: 005)WIRING METHOD USED TO WIRE CEILING CLOSET LIGHT IN BABY'S ROOM NOTAPPROVED. PLASTIC WIRE MOLD NOT APPROVED IN NYC . AMEND ARTICLE300
RSLV 11/17/2016 11/17/2016 12/01/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back