BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z155066
Premises: 116 PINEHURST AVENUE MANHATTAN BIN: 1082358     Block: 2179   Lot: 170
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 116 PINEHURST AV Census Tract:   273
BASEMENT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   A
NEW YORK, NY 10033 Community Board:   112
Special Place Name:   BOILER ROOM
DOB Cross Street(s):   WEST 181 STREET,    HUDSON VIEW GARDENS
Status:   C - JOB IS SIGNED OFF 02/27/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   05/13/2016 Job Start Date:   05/01/2016
Last Change:   02/27/2018 Job End Date:   07/01/2016
Appointment Status:   
Last Inspection By:   JOFFRE PENA       On     01/22/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012804 Licensee Name: GREGORY L BLAU
Firm: 004658 Firm Name: PLATINUM ELECTRICAL GRP
Firm Phone: 718-517-3179  Firm Address: 978 39TH STREET BROOKLYN NY 11219 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $625.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ERIC JENSEN
Owner Business Name: HUDSON VIEW GARDENS, INC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  3- 4WIRE 400A FUSED DISC
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  4#2 & 1#6G
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  FEEDERS.
D. Over 250 MCM  1  SERVICE ENTRANCE
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  NEW PANELS
D. 3 Phase Over 225 AMPS  1  3-4WIRE
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  3  3 GAS, OIL BOILERS. 1 GAS

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS        10  53         
Buildings Total        53           
Total Units : 66 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/27/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  BOILER WIRING & CONTROLS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z155066
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/27/2016 06/27/2016 GYM V (120) (6)
INSPECTION COMMENTS: 3 GAS, OIL BOILERS. 1 GAS BOILER.
 
(2) 01/22/2018 01/22/2018 JRP C R (45) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED, JOB COMPLETE

OBJECTION FOR APPLICATION #: Z155066
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
(BASEMENT) EXISTING 200 AMP SW.
RSLV 06/27/2016 06/27/2016 01/22/2018
 
002 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
(BASEMENT) EXISTING 200 AMP SERVICE.
RSLV 06/27/2016 06/27/2016 01/22/2018
 
003 (220) DOUBLE LUGGING IN SERVICE SWITCH
(BASEMENT) CT
RSLV 06/27/2016 06/27/2016 01/22/2018
 
004 (999) OTHER
(BASEMENT) NO SUPPLEMENTAL ELECTRODE IS PROVIDED 250,53
RSLV 06/27/2016 06/27/2016 01/22/2018
 
005 (999) OTHER
(BASEMENT) WATER JUMPER IS NOT PROPER SIZE 250.53
RSLV 06/27/2016 06/27/2016 01/22/2018
 
006 (999) OTHER
(BASEMENT) NO GROUNDING PROVIDED ALL SERVICE SW,S 250.64
RSLV 06/27/2016 06/27/2016 01/22/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order