BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z154995
Premises: 1012 RIVERSIDE DRIVE MANHATTAN BIN: 1076746     Block: 2139   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 177 FORT WASHINGTON AV Census Tract:   255 Health Area:  8700
2 AND 5 Admin Area:   Z - UPPER MANHATTAN Inspection Area:   A
NEW YORK, NY 10032 Community Board:   112
Special Place Name:   MILSTEIN HOSPITAL
DOB Cross Street(s):   WEST 165 STREET,    WEST 168 STREET
Status:   C - JOB IS SIGNED OFF 10/11/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/10/2016 11:13 AM
Application Entered:   05/10/2016 Job Start Date:   05/10/2016
Last Change:   10/11/2017 Job End Date:   07/15/2016
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     10/10/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010931 Licensee Name: IRA KATZ
Firm: 000639 Firm Name: HARLEY ELECTRIC CO., INC.
Firm Phone: 718-823-8885  Firm Address: 1817 UNIONPORT ROAD BRONX NY 10462 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $71.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: NY PRESBYTERIAN HOSPITAL
Authorized Representative:  GARRY MANCINI
Relationship To Owner:   ELECTRICAL MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002    12  13    15             
005    20  36    12  25             
Buildings Total 32  49    16  40                
Total Units : 137 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/13/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  HEART VALVE EXPANSION

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z154995
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/12/2017 09/13/2017 MQY V (87) (2)
INSPECTION COMMENTS: (A) ISSUED OBJECTIONS
 
(2) 10/10/2017 10/11/2017 DNM C R (22) (0)
INSPECTION COMMENTS: OBJECTION REMOVED.

OBJECTION FOR APPLICATION #: Z154995
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 002)FLEXIBLE CORD SNAKED DOWN A WALL FOR WATER PUMP @CHAPEL DECORFOUNTAIN) FLEXIBLE CORD LOCATED ABOVE CEILING @CHAPEL DECOR FOUNTAIN(400.8)
RSLV 09/12/2017 09/12/2017 10/10/2017
 
002 (999) OTHER
(FLOOR: 005) SIMULTANEOUS TRIP NEEDED ON MULTIWIRE BRANCH CKTS 210.4
RSLV 09/12/2017 09/12/2017 10/10/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order