Electrical Application Details for App #: Z154938
Premises: 41 WEST 72 STREET MANHATTAN BIN: 1028633     Block: 1125   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 41 W 72 ST Census Tract:   157 Health Area:  4000
APT. #9EF Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   CENTRAL PARK EXIT WEST 72 STREET,    COLUMBUS AVENUE
Status:   C - JOB IS SIGNED OFF 10/18/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/05/2016 3:22 PM
Application Entered:   05/05/2016 Job Start Date:   05/06/2016
Last Change:   10/18/2017 Job End Date:   05/06/2017
Appointment Status:   
Last Inspection By:   URIM SYLA       On     08/09/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009742 Licensee Name: HARVEY GILSTON
Firm: 000590 Firm Name: GILSTON ELEC. MAINT. CORP
Firm Phone: 718-294-4400  Firm Address: 453 EAST 175TH STREET BRONX NY 10457 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $134.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: REAL DEAL DECORATIONS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
009  #9EF  20  30  12  20             
Buildings Total 20  30  12  20                
Total Units : 86 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/12/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z154938
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/11/2017 05/12/2017 UMS V (30) (4)
INSPECTION COMMENTS: SEE OBJECTIONS
 
(2) 08/09/2017 08/09/2017 UMS C R (20) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: Z154938
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 009) PANELS INSTALLED IN BATHROOM. NEC 240.24 E
RSLV 05/11/2017 05/11/2017 08/09/2017
 
002 (999) OTHER
(FLOOR: 009) NO DIRECTORY PROVIDED FOR PANELS. NEC 408
RSLV 05/11/2017 05/11/2017 08/09/2017
 
003 (999) OTHER
(FLOOR: 009)OUTLETS, EQUIPMENT NOT GROUNDED. GREEN WIRE OF MC TYPE CABLE NOTCONNECTED ANYWHERE. NEC 314 ( SEE BOTH PANELS)
RSLV 05/11/2017 05/11/2017 08/09/2017
 
004 (999) OTHER
(FLOOR: 009)BEDROOMS. RECEPTACLE OUTLETS SET BACK TO FAR FROM COMBUSTIBLEMATERIAL. NEC 314,20
RSLV 05/11/2017 05/11/2017 08/09/2017