Electrical Application Details for App #: Z154832
Premises: 208 CENTRAL PARK SOUTH MANHATTAN BIN: 1024919     Block: 1030   Lot: 39
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 210 CENTRAL PARK S Census Tract:   137
BASEMENT ELECTRICAL ROOM Admin Area:   Z - UPPER MANHATTAN Inspection Area:   F
NEW YORK, NY 10019 Community Board:   105
Special Place Name:   BASEMENT
DOB Cross Street(s):   CENTRAL PARK EXIT 7 AVENUE,    COLUMBUS CIRCLE
Status:   C - JOB IS SIGNED OFF 09/18/2017
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   04/29/2016 Job Start Date:   04/29/2016
Last Change:   09/18/2017 Job End Date:   12/15/2016
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     09/15/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010144 Licensee Name: JOHN IZZO
Firm: 002205 Firm Name: RESPONSE ELECTRIC INC.
Firm Phone: 718-599-9753  Firm Address: 36 FROST STREET BROOKLYN NY 11211 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,390.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53594     Submittal #: 16A0224  
Owner / Occup:
Owner Business Name: 210 CENTRAL PARK SOUTH IN
Authorized Representative:  ADAM ZERKA
Relationship To Owner:   AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  2  1600AMP SWITCHES
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  8  8SETS 600MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 2
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/29/2016 Notice: 1 - FIRST NOTICE 05/08/2017
Power Issued: 04/29/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  UPGRADE OF ELECTRICAL SERVICE EQUIPMENT IN MAIN ELECTRICAL ROOM

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z154832
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/08/2017 05/08/2017 STP V (45) (3)
INSPECTION COMMENTS: FAIL. NEED MORE TIME FOR THIS INSPECTION ONLY INSPECTED SERVICE SWITCH 1 AND 2 . FULL INSPECT ON REMAINDER, SUPPLEMENT GROUND PATH TO FOOTING NEEDS TO BE CONFIRMED.
 
(2) 09/15/2017 09/18/2017 MLF C R (59) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: Z154832
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT) SER SW 1 MAIN BOND JUMP SIZE
RSLV 05/08/2017 05/08/2017 09/15/2017
 
002 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT) SER SW 2 NOT GROUNDED PER DRAWING AMND 408.60
RSLV 05/08/2017 05/08/2017 09/15/2017
 
003 (999) OTHER
(BASEMENT) SUPPLEMENT GRND DIRECT CONTACT WITH FOOTING 250.52
RSLV 05/08/2017 05/08/2017 09/15/2017