Electrical Application Details for App #: Z154336
Premises: 720 COLUMBUS AVENUE MANHATTAN BIN: 1082743     Block: 1226   Lot: 29
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 730 COLUMBUS AV Census Tract:   181
BASEMENT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   WEST 95 STREET,    WEST 96 STREET
Status:   C - JOB IS SIGNED OFF 12/30/2016
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   03/31/2016 Job Start Date:   03/24/2016
Last Change:   12/30/2016 Job End Date:   03/24/2017
Appointment Status:   
Last Inspection By:   URIM SYLA       On     12/15/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012064 Licensee Name: JOHN STASSI
Firm: 003755 Firm Name: JOHN STASSI
Firm Phone: 718-317-2379  Firm Address: 4347 HYLAN BLVD STATEN ISLAND NY 10312 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
S - SUSTAINABLE ENERGY - GENERAL
Total Fee:  $1,027.50
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53487     Submittal #: 16A0139  
Owner / Occup: BRUCE BARRON
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1 SET #2
B. Over #2 to 1/0  2  2 SETS 1/0 VDF CABLE
C. Over 1/0 to 250 MCM  1  1 SET 3/0
D. Over 250 MCM  9  3 SETS 400MCM,6 SETS 350
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  100AMP
D. 3 Phase Over 225 AMPS  1  600AMP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS        12    155      112 
Buildings Total     12       155          112 
Total Units : 280 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/04/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  75 KW COGEN WITH INVERTER, 600AMPS ATS SWITCH AND 112KVATRANSFORMER FOR CHS/COGEN SYSTEM

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z154336
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/03/2016 11/04/2016 UMS V (110) (1)
INSPECTION COMMENTS: SEE OBJECTION.
 
(2) 12/15/2016 12/19/2016 UMS C R (31) (0)
INSPECTION COMMENTS: PASS. TR-R TYPE FUSE INSTALLED IN LIEU OF FRN TYPE FUSE. SEE FUSE CROSS REFERENCE GUIDE

OBJECTION FOR APPLICATION #: Z154336
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT)FUSES IN 400 AMP RATED SWITCH WHICH IS FED BY LOAD SIDE OF 1600 AMPSERVICE SWITCH DO NOT MATCH WITH FUSES IN ADVISORY BOARD DRAWING. (350 AMP FRN FUSE TYPE NEEDED) AMEND 110.2
RSLV 11/03/2016 11/03/2016 12/15/2016