BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z153734
Premises: 47 FT WASHINGTON AVENUE MANHATTAN BIN: 1063322     Block: 2136   Lot: 86
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 47 FORT WASHINGTON AV Census Tract:   247 Health Area:  0500
UNIT 61 Admin Area:   Z - UPPER MANHATTAN Inspection Area:   B
NEW YORK, NY 10032 Community Board:   112
DOB Cross Street(s):   WEST 160 STREET,    WEST 161 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/23/2016 10:58 AM
Application Entered:   02/23/2016 Job Start Date:   02/23/2016
Last Change:   08/22/2025 Job End Date:   08/25/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     08/22/2016      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011234 Licensee Name: JOSEPH ADAMO
Firm: 003747 Firm Name: MEGA ELEC'L CONTR'G, INC
Firm Phone: 718-232-3632  Firm Address: 8023 NEW UTRECHT AVENUE BROOKLYN NY 11214 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $74.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DANIELA MARIN
Owner Business Name: ELOD STUDIO LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  12/2030
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
006    30  40  14               
Buildings Total 30  40  14                  
Total Units : 89 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 08/23/2016
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  GENERAL WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z153734
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/02/2016 08/04/2016 MQY N (36) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR HE SAID HIS ELECTRICIAN CANT MAKE IT FOR TODAYS APPT. NO ONE SHOWED UP
 
(2) 08/22/2016 08/23/2016 GYM V (85) (5)
INSPECTION COMMENTS: AFCI MISSING.

OBJECTION FOR APPLICATION #: Z153734
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 006) KITCHEN.
OPEN 08/22/2016 08/22/2016
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 006) DRY WALL SCREWS.
OPEN 08/22/2016 08/22/2016
 
003 (999) OTHER
(FLOOR: 006)MIN 2 20 AMP SMALL APPLIANCE CIRCUITS REQ'D 210.11 KITCHEN
OPEN 08/22/2016 08/22/2016
 
004 (999) OTHER
(FLOOR: 006) COMBINATION AFCI REQ'D 210.12
OPEN 08/22/2016 08/22/2016
 
005 (999) OTHER
(FLOOR: 006) EXTENDER MISSING OUTLET BOXES 314.20
OPEN 08/22/2016 08/22/2016