BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z153599
Premises: 221 WEST 82 STREET MANHATTAN BIN: 1076247     Block: 1230   Lot: 7501
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 221 W.82ND ST Census Tract:   171 Health Area:  3400
APT 11CD Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   AMSTERDAM AVENUE,    BROADWAY
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/12/2016 9:20 AM
Application Entered:   02/12/2016 Job Start Date:   02/12/2016
Last Change:   08/22/2025 Job End Date:   02/12/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   URIM SYLA       On     06/15/2016      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012289 Licensee Name: STEVE MOTTES
Firm: 003031 Firm Name: GSA ELECTRIC CORP.
Firm Phone: 718-922-3300  Firm Address: 9302 DITMAS AVENUE BROOKLYN NY 11236 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
010730 MARGOLIN, ALBERT 003031 GSA ELECTRIC CORP.
012290 MARGOLIN, GREGG 003031 GSA ELECTRIC CORP.
010730 MARGOLIN, ALBERT 003031 GSA ELECTRIC CORP.

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $99.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JACOB FRUMKIN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
011  11CD  20  34  18  23             
Buildings Total 20  34  18  23                
Total Units : 99 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 06/16/2016
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  REWIRE ENTIRE APARTMENT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z153599
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/29/2016 03/01/2016 MQY V (39) (3)
INSPECTION COMMENTS: ISSUED OBJECTIONS
 
(2) 06/15/2016 06/16/2016 UMS V R (40) (2)
INSPECTION COMMENTS: SEE OBJECTIONS

OBJECTION FOR APPLICATION #: Z153599
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 011)RECEPTACLES ON BASE MOLDING SET BACK ON WOOD WITH OUT PROTECTIONTHROUGH OUT (314.20)
RSLV 02/29/2016 02/29/2016 06/15/2016
 
002 (999) OTHER
(FLOOR: 011)AFCI NEEDED ON ALL NEW BRANCH CIRCUITS(LIGHT & RECEPTACLES) (210.12)
RSLV 02/29/2016 02/29/2016 06/15/2016
 
003 (999) OTHER
(FLOOR: 011) BURIED SPLICE BOX FOR PANEL (314.29)
RSLV 02/29/2016 02/29/2016 06/15/2016
 
004 (999) OTHER
(FLOOR: 011)NEUTRAL WIRES CONNECTED TO EQUIPMENT GROUNDING IN PANEL. NEC 250.24
OPEN 06/15/2016 06/15/2016
 
005 (999) OTHER
(FLOOR: 011)NEWLY INSTALLED AFCI CIRCUIT BREAKERS NOT OF COMBINATION TYPE. NEC210.12
OPEN 06/15/2016 06/15/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.