BIS Menu  |  Comments  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z153498
Premises: 235 CENTRAL PARK WEST MANHATTAN BIN: 1031233     Block: 1197   Lot: 36
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 239 CENTRAL PARK W Census Tract:   169 Health Area:  3500
APT. 5 E Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   CENTRAL PARK WEST,    COLUMBUS AVENUE
Status:   C - JOB IS SIGNED OFF 10/31/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/04/2016 2:31 PM
Application Entered:   02/04/2016 Job Start Date:   02/04/2016
Last Change:   10/31/2016 Job End Date:   10/22/2016
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     10/28/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012768 Licensee Name: SENAD MEHOVIC
Firm: 004614 Firm Name: E & M ELECTRICAL NY CORP
Firm Phone: 718-281-0158  Firm Address: 193-02 NORTHERN BLVD FLUSHING NY 11358 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $57.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: VICTOR
Owner Business Name: PRINCIPE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
MZ5    10                 
Buildings Total 10                    
Total Units : 21 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/17/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRED KITCHEN ONLY.EVRETHING ELSE IS EXISTING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z153498
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/13/2016 10/17/2016 GYM V (40) (4)
INSPECTION COMMENTS: SEE APPL. # Z153387
 
(2) 10/28/2016 10/31/2016 PHG C R (60) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: Z153498
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(FLOOR: 005) SPLICE BOX
RSLV 10/13/2016 10/13/2016 10/28/2016
 
002 (999) OTHER
(FLOOR: 005) AFCI MUST PROTECT ENTIRE NEW CIRCUIT 210.12
RSLV 10/13/2016 10/13/2016 10/28/2016
 
003 (999) OTHER
(FLOOR: 005) SEPARATE 20 AMP CIRCUIT FOR BATH RECEPTACLES 210.11
RSLV 10/13/2016 10/13/2016 10/28/2016
 
004 (999) OTHER
(FLOOR: 005) MC CABLE MISSING GREEN WIRES 110.2
RSLV 10/13/2016 10/13/2016 10/28/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.