| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
1 |
1-800 AMP |
| E. Over 1200 AMPS |
11 |
2-1600,2-2000,1-3000,4-4 |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
370 |
370-#2 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
12 |
12-250 MCM |
| D. Over 250 MCM |
56 |
16-500,30-600,20-750 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
116 |
100 AMP APT.PANELS |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
246 |
200 AMP APT.PANELS |
| C. 3 Phase Up to 225 AMPS |
31 |
26-100 AMP |
| D. 3 Phase Over 225 AMPS |
1 |
9-400,7-600,1-800,1-1600 |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 002) FUSE IN TOP 2 NOT MATCHING THE DRAWING. |
RSLV |
08/24/2018 |
08/24/2018 |
05/06/2019 |
| |
| 002 |
(999) |
OTHER (FLOOR: 002) RACEWAY BONDING ON FEEDERE ARE UNDER SIZE. 250.122(F) |
RSLV |
08/24/2018 |
08/24/2018 |
05/06/2019 |
| |
| 003 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (FLOOR: 042)MDB-LS-R AND DP-L-CON ON 42ND FLOOR ARE OVER-FUSED, AT THE BSMT.408.36 |
RSLV |
08/24/2018 |
08/24/2018 |
06/03/2023 |
| |
| 004 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 042) BREAKERS IN GENERATOR ROOM NOT MATCHING THE DRAWING. |
RSLV |
08/24/2018 |
08/24/2018 |
06/03/2023 |
| |
| 005 |
(999) |
OTHER (ALL FLOORS)DURABLE 480V STICKERS NEEDED ON ALL HI VOLTAGE EQUIPMENTS. AMEN408.60(C) |
RSLV |
08/24/2018 |
08/24/2018 |
05/06/2019 |
| |
| 006 |
(999) |
OTHER (ALL FLOORS) ARC FLASH STICKERS NEEDED ON ALL EQUIPMENTS. 110.16 |
RSLV |
08/24/2018 |
08/24/2018 |
05/06/2019 |
| |
| 007 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT)FIRE PUMP SERVICE SWITCH AND FUSE SIZE NOT ACCORDING TO DRAWING. |
RSLV |
08/24/2018 |
08/24/2018 |
06/03/2023 |
| |
| 008 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT)TRANSFORMER SEC. SWITCH DOES NOT HAVE NEUTRAL, AS PER DRAWING. |
RSLV |
08/24/2018 |
08/24/2018 |
05/06/2019 |
| |
| 009 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) TRANSFORMERS SEC. SWITCH NOT BONDED. |
RSLV |
08/24/2018 |
08/24/2018 |
05/06/2019 |
| |
| 010 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) FUSE DON'T MATCH DRAWING IN SERVICE A ODP/ SECTION 1 |
RSLV |
08/24/2018 |
08/24/2018 |
05/06/2019 |
| |
| 011 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) ROOM LAYOUT HAVE ADDITIONAL EQUIPMENTS. |
RSLV |
08/24/2018 |
08/24/2018 |
06/03/2023 |
| |
| 012 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) FIRE PUMP SWITCH NEED GEC. |
RSLV |
08/24/2018 |
08/24/2018 |
05/06/2019 |
| |
| 013 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) S.SW #3B AND 5B HAVE NO GRND. STRAPS. |
RSLV |
08/24/2018 |
08/24/2018 |
06/03/2023 |
| |
| 014 |
(999) |
OTHER (BASEMENT)ALL SERVICE, AND DISCONNECT SWITCHES NEED TO BE MARKED FOR LOCATIONOF LOADS. 230.70(B)/ 110.22 |
RSLV |
08/24/2018 |
08/24/2018 |
05/06/2019 |
| |
| 015 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (ALL FLOORS) OCP OVERSIZED FOR AC UNITS. ART. 240.3. |
RSLV |
05/06/2019 |
05/06/2019 |
06/03/2023 |
| |
| 016 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (ALL FLOORS) KO SEALS ARE MISSING IN PANELS T-OUT. ART 110.12 |
RSLV |
05/06/2019 |
05/06/2019 |
06/03/2023 |
| |
| 017 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE (ALL FLOORS) BUSHING MISSING ON APARTMENTS FEEDERS. ART. 300.4 |
RSLV |
05/06/2019 |
05/06/2019 |
06/03/2023 |
| |
| 018 |
(999) |
OTHER (ALL FLOORS)NO ACCESS PANELS PROVIDED FOR TROUGHS IN ELECTRICAL CLOSETS. ART.314.29. |
RSLV |
05/06/2019 |
05/06/2019 |
06/03/2023 |
| |
| 019 |
(999) |
OTHER (ALL FLOORS) CONDUITS ARE NOT SUPPORTED BETWEEN FLOORS. ART. 358.30. |
RSLV |
05/06/2019 |
05/06/2019 |
06/03/2023 |
| |
| 020 |
(999) |
OTHER (ALL FLOORS) PANEL DIRECTORY NOT PROVIDED T-OUT. ART. 408.4 |
RSLV |
05/06/2019 |
05/06/2019 |
06/03/2023 |
| |
| 021 |
(999) |
OTHER (ALL FLOORS)ALL FLOORS DISTRIBUTION PANELS, FEEDERS NOT BONDED. ART. 300.10. |
RSLV |
05/06/2019 |
05/06/2019 |
06/03/2023 |
| |
| 022 |
(999) |
OTHER (ALL FLOORS)LAUNDRY ROOMS RECEPTACLES NOT GFCI PROTECTED. ART. 210.8. |
RSLV |
05/06/2019 |
05/06/2019 |
06/03/2023 |
| |
| 023 |
(999) |
OTHER (ALL FLOORS) UNDERSIZED GROUND FOR DRYER RECEPTACLES. TABLE 250.122 |
RSLV |
05/06/2019 |
05/06/2019 |
06/03/2023 |
| |
| 024 |
(999) |
OTHER (ALL FLOORS)DISCONNECT MEANS ARE NOT PROVIDED FOR KITCHEN OVEN. ART. 422.30. |
RSLV |
05/06/2019 |
05/06/2019 |
06/03/2023 |
| |
| 025 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR)SERVICE SWITCH #3B LOAD SIDE CONDUCTOR NOT AS PER DRAWING. AM.110.2. |
RSLV |
05/06/2019 |
05/06/2019 |
06/03/2023 |
| |
| 026 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR) 2; 60 AMP. SERVICE SWITCHES NOT BONDED. AM. 110.2 |
RSLV |
05/06/2019 |
05/06/2019 |
06/03/2023 |