Electrical Application Details for App #: Z152272
Premises: 100 RIVERSIDE BOULEVARD MANHATTAN BIN: 1087705     Block: 1171   Lot: 7505
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 100 RIVERSIDE BLVD Census Tract:   151 Health Area:  3900
21A Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10069 Community Board:   107
DOB Cross Street(s):   WEST 64 STREET,    WEST 65 STREET
Status:   C - JOB IS SIGNED OFF 11/21/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/29/2015 3:24 PM
Application Entered:   10/29/2015 Job Start Date:   10/29/2015
Last Change:   11/21/2016 Job End Date:   05/27/2016
Appointment Status:   
Last Inspection By:   URIM SYLA       On     10/27/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011207 Licensee Name: ALBERT O STIEFEL
Firm: 001843 Firm Name: POLYPHASE ELECTRIC INC.
Firm Phone: 718-392-0885  Firm Address: 41-20 38TH STREET L.I.C. NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $48.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: G. BLANCK
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  1-PHASE 60A
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
021               
Buildings Total                   
Total Units : 3 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/13/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  FIRE JOB - TERRACE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z152272
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/13/2016 07/13/2016 TUR V (30) (3)
INSPECTION COMMENTS: INSTALLATION NOT COMPLETE DO NOT USE UNTIL EQUIPOTENTIAL BONDING GRID IS INSTALLED AND INSPECTED
 
(2) 10/27/2016 10/28/2016 UMS C R (40) (0)
INSPECTION COMMENTS: PASS. OBJECTIONS CLEARED

OBJECTION FOR APPLICATION #: Z152272
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ROOF) 110.14 DOUBLE LUGGING OF GROUNDS IN CONTROL PANEL
RSLV 07/13/2016 07/13/2016 10/27/2016
 
002 (999) OTHER
(ROOF) 110.21,22 DISCONNECT AND BREAKER MUST BE CLEARLY LABELED WITHDURABLE MEANS FOR PURPOSE INTENDED AND OCP (SPA EMERGENCY SHUT DOWN)
RSLV 07/13/2016 07/13/2016 10/27/2016
 
003 (999) OTHER
(ROOF)680.42, 680.26(B)(2)(A) AND (B) INSTALLATION MUST COMPLY WITH NEC680.42 PART TWO WHICH REFERS TO 680.26(B)(2)(A) AND (B)EQUIPOTENTIAL BONDING GRID FOR HOT TUB (MUST COMPLY WITH INSTALL ONSLAB OUTDOORS
RSLV 07/13/2016 07/13/2016 10/27/2016