NYC Department of Buildings
Electrical Application Details for App #: Z152027
Premises: 508 WEST 134 STREET MANHATTAN BIN: 1059745     Block: 1987   Lot: 41
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 508 W 134 ST Census Tract:   219 Health Area:  1100
FLOORS 1 - 5 Admin Area:   Z - UPPER MANHATTAN Inspection Area:   B
NEW YORK, NY 10031 Community Board:   109
Special Place Name:   AMSTERDAM AVE & BROADWAY
Related Job Number:    110041124
DOB Cross Street(s):   AMSTERDAM AVENUE,    BROADWAY
Status:   C - JOB IS SIGNED OFF 01/18/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/15/2015 3:25 PM
Application Entered:   10/15/2015 Job Start Date:   10/15/2015
Last Change:   01/18/2017 Job End Date:   09/30/2016
Appointment Status:   
Last Inspection By:   URIM SYLA       On     01/12/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012567 Licensee Name: MOHAMMOD Q BHUYAIN
Firm: 002997 Firm Name: RELIANT ELEC'L CONT'G INC
Firm Phone: 718-636-8898  Firm Address: 628 CLASSON AVENUE BROOKLYN NY 11238 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $935.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: NICK DEACETIS
Owner Business Name: MDG DESIGN & CONST
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  200 AMP PLP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400 AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  16  15 SETS OF #4AWG 1 SET OF
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1 SET OF 3/0 FOR PLP
D. Over 250 MCM  1  1 SET 500 MCM FEEDER
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  15  16/24 - 125 AMP 3 WIRE
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  42 CCT 200 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  2  2 HP 208V

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS             
GND    26  32  21  26             
002    27  34  12  24  27             
003    27  34  12  24  27             
005    27  34  12  24  27             
Buildings Total 113  138  44  95  113              
Total Units : 505 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 15 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 16 - Removed Meters 0 = Total Meters 16

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/15/2015 Notice: 1 - FIRST NOTICE 11/03/2016
Power Issued: 10/15/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL 400 AMP SERVICE SWITCH WITH 15 GANG 208V 3 WIRE METER PEN WITH 200 AMP 3 PHASE FOR PLP AREA

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z152027
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/02/2016 11/03/2016 MQY V (101) (5)
INSPECTION COMMENTS: INSPECTED. ISSUED OBJECTIONS. NO FUSES INSTALLED IN 400A SS, TEMP FED FROM PLP PANEL
 
(2) 01/12/2017 01/12/2017 UMS C R (35) (0)
INSPECTION COMMENTS: PASS. OBJECTIONS CLEARED

OBJECTION FOR APPLICATION #: Z152027
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) KO BROKEN IN 3RD SECTION OF METER BANK (110.3)
RSLV 11/02/2016 11/02/2016 01/12/2017
 
002 (999) OTHER
(BASEMENT)NO WORKING SPACE FOR ELECTRICAL EQUIPMENT (CONCRETE STAGE DOESNTALLOW WORKING SPACE (110.26)
RSLV 11/02/2016 11/02/2016 01/12/2017
 
003 (999) OTHER
(BASEMENT) 200 AMP SS SERVICE RACEWAY NOT BONDED (250.92)
RSLV 11/02/2016 11/02/2016 01/12/2017
 
004 (999) OTHER
(BASEMENT)MORE THAN 2 CONDUCTORS UNDER A SPLIT BOLT FOR THE FIRE ALARM(110.14A)
RSLV 11/02/2016 11/02/2016 01/12/2017
 
005 (999) OTHER
(BASEMENT)SIMULTANEOUS TRIP NEEDED ON MULTIWIRE BRANCH CKT IN PLP PANEL(210.4)
RSLV 11/02/2016 11/02/2016 01/12/2017