Electrical Application Details for App #: Z151118
Premises: 240 WEST 98 STREET MANHATTAN BIN: 1056384     Block: 1869   Lot: 7503
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 240 W 98 ST Census Tract:   183 Health Area:  3110
13 B AND C Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   BROADWAY,    WEST END AVENUE
Status:   C - JOB IS SIGNED OFF 10/05/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/12/2015 8:23 AM
Application Entered:   08/12/2015 Job Start Date:   08/12/2015
Last Change:   10/05/2017 Job End Date:   12/31/2016
Appointment Status:   
Last Inspection By:   JOFFRE PENA       On     08/29/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009301 Licensee Name: GEORGE CRUZ
Firm: 000367 Firm Name: CRUZ ELECTRIC CORP.
Firm Phone: 718-299-5100  Firm Address: 4 EAST TREMONT AVENUE BRONX NY 10453 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $157.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BRIAN SALSBERG
Owner Business Name: N/A
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  2 SINGLE PHASE 24 CIRCUT
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
013    82  58  37               
Buildings Total 82  58  37                  
Total Units : 181 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/24/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z151118
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/23/2016 06/24/2016 UMS V (35) (5)
INSPECTION COMMENTS: RISER NOT INSPECTED
 
(2) 08/29/2016 09/09/2016 JRP C R (40) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED. INSPECTION REMOVED.

OBJECTION FOR APPLICATION #: Z151118
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 013)DEFECTIVE AFCI IS IN USE. AFCI DOES NOT TRIP. AMEND 110.2
RSLV 06/23/2016 06/23/2016 08/29/2016
 
002 (999) OTHER
(FLOOR: 013)HVAC EQUIPMENT NOT GROUNDED PROPERLY. NO MECHANICAL CONNECTIONPROVIDED. NEC 314.4
RSLV 06/23/2016 06/23/2016 08/29/2016
 
003 (999) OTHER
(FLOOR: 013)KITCHEN , LAUNDRY PLUG MOLD RECEPTACLES NOT GROUNDED. NEC 250 146
RSLV 06/23/2016 06/23/2016 08/29/2016
 
004 (999) OTHER
(FLOOR: 013)KITCHEN , LAUNDRY PLUG MOLD RECEPTACLES NOT GFI PROTECTED. 210.8
RSLV 06/23/2016 06/23/2016 08/29/2016
 
005 (999) OTHER
(FLOOR: 013) MASTER BATH RECEPTACLES NOT GFI PROTECTED. 210.8
RSLV 06/23/2016 06/23/2016 08/29/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.