BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z150687
Premises: 169 WEST 72 STREET MANHATTAN BIN: 1029916     Block: 1144   Lot: 1
   
Application Completed and Certified

Filed: 267 AMSTERDAM AV Census Tract:   157 Health Area:  4000
STORE Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   WEST 72 STREET,    WEST 73 STREET
Status:   C - JOB IS SIGNED OFF 10/09/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/21/2015 7:05 AM
Application Entered:   07/21/2015 Job Start Date:   07/21/2015
Last Change:   10/09/2015 Job End Date:   07/21/2016
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     08/13/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011509 Licensee Name: MORGAN J TOREN
Firm: 002978 Firm Name: A.C. MORGAN ELECTRIC
Firm Phone: 718-549-6800  Firm Address: 3601 RIVERDALE AVENUE BRONX NY 10463 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $380.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   PIZZERIA
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: HOWARD ESTRIN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    22  12  14            40 
Buildings Total 22  12  14                 40 
Total Units : 90 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/21/2015 Notice: C - CALL TO OFFICE 08/17/2015
Power Issued: 07/21/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z150687
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/05/2015 08/11/2015 TOR V E (50) (11) Y
INSPECTION COMMENTS: DID NOT INSPECT 1ST FLOOR
 
(2) 08/05/2015 08/17/2015 TOR V X G (50) (0) Y
INSPECTION COMMENTS: DID NOT INSPECT FIRST FLOOR
 
(3) 08/13/2015 08/20/2015 BMP C R E (65) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z150687
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
CEL: X- FORMER NOT LISTED 110.2
RSLV 08/05/2015 08/05/2015 08/13/2015
 
002 (999) OTHER
CEL: NO HANDLE TIES PANEL 210.4
RSLV 08/05/2015 08/05/2015 08/13/2015
 
003 (999) OTHER
CEL: WALKIN FRIDGE PLASTIC CONNECTS T-OUTS 110.2
RSLV 08/05/2015 08/05/2015 08/13/2015
 
004 (999) OTHER
CEL: WALKIN FREEZER DISCONNECT NO SPACE 110.2
RSLV 08/05/2015 08/05/2015 08/13/2015
 
005 (999) OTHER
CEL: EMT NOT SUPPORTED T-OUT 358.30
RSLV 08/05/2015 08/05/2015 08/13/2015
 
006 (999) OTHER
CEL: BOS OVERCROWDED (BOX FILL) 314.16
RSLV 08/05/2015 08/05/2015 08/13/2015
 
007 (999) OTHER
CEL: BOXS NOT SUPPORTED T-OUT
RSLV 08/05/2015 08/05/2015 08/13/2015
 
008 (999) OTHER
CEL: DERAITING TROUFT 310.15 B3A
RSLV 08/05/2015 08/05/2015 08/13/2015
 
009 (999) OTHER
CEL GROUNDING ELECTRODE CONDUCTOR UNDERSIZED 250.66
RSLV 08/05/2015 08/05/2015 08/13/2015
 
010 (999) OTHER
CEL BONDING ON LINE SIDE OF SERVICE 250.4
RSLV 08/05/2015 08/05/2015 08/13/2015
 
011 (999) OTHER
CEL OVEN NOT LISTED 110.2
RSLV 08/05/2015 08/05/2015 08/13/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.