| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER GRND: NO CONTINUITY OF PIE BETWEEN FIXTURE.. 300.12 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 002 |
(999) |
OTHER T-OUT: KO SEALS OPEN ON ALL FIXTURES.. 110.12 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 003 |
(999) |
OTHER GRND: LIGHT FIXTURE USED AS RACEWAY 1ST FLOOR.. 410.64 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 004 |
(999) |
OTHER T-OUT: LIGHT FIXTURE GROUNDED WITH SHEET METAL SCREW.. 250.8 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 005 |
(999) |
OTHER BSMT: E.M.T.NOT SUPPORTED.. 358.30 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 006 |
(999) |
OTHER (FLOOR: 001) NO CONTINUITY BETWEEN CONDUIT AND FIXTURE |
RSLV |
01/11/2016 |
01/11/2016 |
07/23/2024 |
| |
| 007 |
(999) |
OTHER (FLOOR: 001) KO'S T OUT FIXTURES |
RSLV |
01/11/2016 |
01/11/2016 |
05/19/2016 |
| |
| 008 |
(999) |
OTHER (FLOOR: 001) FIXTURE USED AS RACEWAY |
RSLV |
01/11/2016 |
01/11/2016 |
05/19/2016 |
| |
| 009 |
(999) |
OTHER (FLOOR: 001) SHEET METAL SCREWS USED TO GROUND FIXTURES |
RSLV |
01/11/2016 |
01/11/2016 |
07/23/2024 |
| |
| 010 |
(999) |
OTHER (FLOOR: 001) EMT NO SUPPORT |
RSLV |
01/11/2016 |
01/11/2016 |
05/19/2016 |
| |
| 011 |
( 45) |
FIXTURE NOT INSTALLED IN AN APPROVED MANNER (BASEMENT) FIXTURES |
RSLV |
05/19/2016 |
05/19/2016 |
07/23/2024 |
| |
| 012 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (GROUND FLOOR) FIXTURES ARMORED NOT TERMINATED. |
RSLV |
05/19/2016 |
05/19/2016 |
07/23/2024 |