BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z149731
Premises: 520 WEST 114 STREET MANHATTAN BIN: 1057035     Block: 1885   Lot: 43
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 520 W 114 ST Census Tract:   199 Health Area:  2310
BASEMENT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10025 Community Board:   109
DOB Cross Street(s):   AMSTERDAM AVENUE,    BROADWAY
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/21/2015 11:14 AM
Application Entered:   05/21/2015 Job Start Date:   05/21/2015
Last Change:   08/22/2025 Job End Date:   12/01/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   VINCENT CASTALDO       On     05/01/2019      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012388 Licensee Name: ANDREW LIVADITIS
Firm: 000442 Firm Name: DOUMAS ELECTRIC INC.
Firm Phone: 212-961-1305  Firm Address: 560 BARRY STREET BRONX NY 10474 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
011174 BOETTCHER, THOMAS 000442 DOUMAS ELECTRIC INC.

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $2,545.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARK KERMAN
Owner Business Name: COLUMBIA UNVERSITY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  6  200A 3 PHASE
C. 201 Up to 600 AMPS  1  600A 3 PHASE
D. 601 Up to 1200 AMPS  3  800 A 3 PHASE
E. Over 1200 AMPS  1  2500A 3 PHASE
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  6  #2/0
D. Over 250 MCM  10  600 & 350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  2  42 CKT 3 PHASE
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 42 #4-Wire 0 #10-Wire 1
Existing Meters 42 + New Meters 42 - Removed Meters 42 = Total Meters 42

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 05/21/2015 Notice: 1 - FIRST NOTICE 05/01/2019
Power Issued: 05/21/2015 Response:  

Follow-Up:
Contractor's Comments:  NEW INCOMING ELECTRICAL SERVICE. RISERS TO APARTMENTS EXISTING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z149731
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/12/2019 04/12/2019 MJD V (40) (1)
INSPECTION COMMENTS: FAIL, NO SHOW, VISUAL INSPECTION ONLY
 
(2) 05/01/2019 05/01/2019 VTC V R (184) (9)
INSPECTION COMMENTS: FAIL

OBJECTION FOR APPLICATION #: Z149731
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(BASEMENT)VISUAL INSPECTION OBSERVED 2 SERVICE SWITCHES TOTAL OF 3100 AMPS,NEED A/B APPROVAL AM. 110.2
RSLV 04/12/2019 04/12/2019 05/01/2019
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(BASEMENT) FUSING FOR BOILER PANEL OVER SIZED
OPEN 05/01/2019 05/01/2019
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(BASEMENT) BOTH PANELS NEED DIRECTORIES
OPEN 05/01/2019 05/01/2019
 
004 (999) OTHER
(BASEMENT)CONTRACTOR NEEDS TO OPEN NEW APP. TO REFLECT JUST 1 2500 AMP.SERVICE SWITCH, SHO4 4 PANELS OVER 225 AMPS., 2 PANELS UP TO 225 A.AND CORRECT FEEDER AMOUNT
OPEN 05/01/2019 05/01/2019
 
005 (999) OTHER
(BASEMENT) RACEWAY NOT CONTINUOUS WITH G.E.C. 250.62C
OPEN 05/01/2019 05/01/2019
 
006 (999) OTHER
(BASEMENT) DURABLE LABELS NOT PROVIDED FOR EQUIPMENT 110.22
OPEN 05/01/2019 05/01/2019
 
007 (999) OTHER
(BASEMENT)SIMULTANEOUS DISCONNECT NOT PROVIDED AND GROUPING 210.4B,D
OPEN 05/01/2019 05/01/2019
 
008 (999) OTHER
(BASEMENT) FIRESTOP NOT PROVIDED 300.21
OPEN 05/01/2019 05/01/2019
 
009 (999) OTHER
(BASEMENT) INTERSYSTEM GROUND NOT PROVIDED 250.94
OPEN 05/01/2019 05/01/2019
 
010 (999) OTHER
(BASEMENT)NEUTRAL DISCONNECT LINK NOT PROVIDED FOR SWITCHGEAR 408.60 NYC AMD.
OPEN 05/01/2019 05/01/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.