BIS Menu  |  Certs. Occupancy   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z148594
Premises: 2689 BROADWAY MANHATTAN BIN: 1056548     Block: 1874   Lot: 52
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 230 W 103 ST Census Tract:   191 Health Area:  3110
BASEMENT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   BROADWAY,    WEST END AVENUE
Status:   C - JOB IS SIGNED OFF 06/25/2021
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/16/2015 12:02 PM
Application Entered:   03/16/2015 Job Start Date:   03/16/2015
Last Change:   06/25/2021 Job End Date:   03/20/2015
Appointment Status:   
Last Inspection By:   GIUSEPPE IMBURGIA       On     06/25/2021      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  

License #: 012388 Licensee Name: ANDREW LIVADITIS
Firm: 000442 Firm Name: DOUMAS ELECTRIC INC.
Firm Phone: 212-961-1305  Firm Address: 560 BARRY STREET BRONX NY 10474 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
011174 BOETTCHER, THOMAS 000442 DOUMAS ELECTRIC INC.

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $85.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOANNE VARGAS
Owner Business Name: WSFSSH
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/16/2015 Notice:  
Power Issued: 03/16/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL NEW ELECTRIC METER

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z148594
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/25/2021 06/25/2021 GIG C (56) (0) Y
INSPECTION COMMENTS: INSPECTION PASSED




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Certs. Occupancy