Electrical Application Details for App #: Z148417
Premises: 601 WEST 59 STREET MANHATTAN BIN: 1088869     Block: 1171   Lot: 165
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1 W END AV Census Tract:   151 Health Area:  3900
GROUND Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
Related Job Number:    121333342
DOB Cross Street(s):    11 AVENUE,    WEST 60 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/03/2015 12:19 PM
Application Entered:   03/03/2015 Job Start Date:   09/01/2015
Last Change:   08/22/2025 Job End Date:   09/01/2018
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   MARCIN DUBAJ       On     04/27/2022      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 012512 Licensee Name: WARREN BUBAK
Firm: 003078 Firm Name: KNIGHT ELEC'L SERV. CORP.
Firm Phone: 212-989-2333  Firm Address: 599 11TH AVENUE, 7TH FLOOR NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $1,871.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SCOTT THOMPSON
Owner Business Name: RIVERSIDE CENTER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  10  
B. Each Additional 10 Floors Or Less  7  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 04/28/2022
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z148417
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/27/2022 04/28/2022 MJD V (115) (3)
INSPECTION COMMENTS: FAIL, INSPECTION COMPLETE

OBJECTION FOR APPLICATION #: Z148417
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(FLOOR: 022) ART. 250.24 22 FLOOR ALL CAR LIGHT DISCONNECT SWITCHES
OPEN 04/27/2022 04/27/2022
 
002 ( 42) BUSHINGS ARE MISSING OR LOOSE
(ALL FLOORS)ART. 300.4 BUSHINGS MISSING 22 FLOOR PANEL HYDRO ELEVATOR CONTROLLER
OPEN 04/27/2022 04/27/2022
 
003 (999) OTHER
(ALL FLOORS)FILE NEW APPLICATION TO ADD 5 ELEVATORS FOR TOTAL 15, AND 9ADDITIONAL FLOORS FOR TOTAL 16
OPEN 04/27/2022 04/27/2022



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.