Electrical Application Details for App #: Z148350
Premises: 2394 7 AVENUE MANHATTAN BIN: 1060372     Block: 2025   Lot: 34
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 2394 7 AV Census Tract:   230 Health Area:  1000
BASEMENT, RISER, ROOF Admin Area:   Z - UPPER MANHATTAN Inspection Area:   B
NEW YORK, NY 10030 Community Board:   110
DOB Cross Street(s):   WEST 139 STREET,    WEST 140 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/25/2015 9:44 PM
Application Entered:   02/25/2015 Job Start Date:   02/27/2015
Last Change:   08/22/2025 Job End Date:   07/27/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   PANAYOTEDIS, STEPHEN       On     06/11/2016      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 012520 Licensee Name: RICHARD E CHIAPPA
Firm: 004443 Firm Name: RC3 ELECTRIC, LLC
Firm Phone: 718-881-8070  Firm Address: 4465 BRONX BLVD BRONX NY 10470 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $221.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   CELL SITE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GEORGE OBSUTH
Owner Business Name: VERIZON WIRELESS
Authorized Representative:  GEORGE OBSUTH
Relationship To Owner:   CM


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  $30
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  $45
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  $50
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                       
ROF        50         
Buildings Total        50           
Total Units : 56 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 02/25/2015 Notice: C - CALL TO OFFICE 06/13/2016
Power Issued: 02/25/2015 Response:  

Follow-Up:
Contractor's Comments:  200AMP SERVICE, RISER, EQUIPMENT WIRING ON ROOF INCLUDING 50KW GEN

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z148350
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/10/2016 02/11/2016 GYM V (55) (2)
INSPECTION COMMENTS: INSPECTED BSMT ONLY.
 
(2) 03/18/2016 03/21/2016 CPP N (20) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(3) 04/02/2016 05/03/2016 UMS V R (40) (1)
INSPECTION COMMENTS: INSPECTION COMPLETE
 
(4) 06/01/2016 06/02/2016 UMS N (60) (0) Y
INSPECTION COMMENTS: INSPECTOR HAVE NO SIGNAL TO SUBMIT WORK I MUST ENTER ON HIS BEHALF
 
(5) 06/11/2016 06/13/2016 STP V X (30) (1)
INSPECTION COMMENTS: FAIL. PREVIOUS VIOLATION NOT REMOVED.

OBJECTION FOR APPLICATION #: Z148350
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) GROUNDING IS NOT PROVIDED IN ALL SERVICE SW'S.
RSLV 02/10/2016 02/10/2016 04/02/2016
 
002 (999) OTHER
(BASEMENT) MAX 6 SERVICE SW;S REQ,D ART 230.71
RSLV 02/10/2016 02/10/2016 04/02/2016
 
003 (999) OTHER
(BASEMENT)NEW SERVICE SWITCH INSTALLED EXCEEDS MAXIMUM NUMBER OF SERVICESWITCHES ALLOWED . NEC 230
OPEN 04/02/2016 04/02/2016
 
004 (999) OTHER
(BASEMENT) CON ED BOX ALTERED FOR NEW SERVICE SWITCH FEED 110.3
OPEN 06/11/2016 06/11/2016