BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z147320
Premises: 250 RIVERSIDE DRIVE MANHATTAN BIN: 1057065     Block: 1887   Lot: 40
   
Application Completed and Certified

Filed: 250 RIVERSIDE DR Census Tract:   183 Health Area:  3110
BOILER ROOM Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   WEST 97 STREET,    WEST 98 STREET
Status:   C - JOB IS SIGNED OFF 03/03/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/10/2014 3:40 PM
Application Entered:   12/10/2014 Job Start Date:   12/10/2014
Last Change:   03/03/2015 Job End Date:   12/23/2014
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     01/09/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011221 Licensee Name: JOHN FRANCICA
Firm: 002575 Firm Name: JJD ELEC'L SERV. & INST C
Firm Phone: 718-354-6566  Firm Address: 220 CITY ISLAND AVENUE BRONX NY 10464 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
8 - BOILER/BURNER WIRING
Total Fee:  $52.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOANN KLEBONAS
Owner Business Name: DEBORA ASSOCIATES L.P.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/06/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z147320
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/26/2014 01/06/2015 UMS A (35) (3) Y
INSPECTION COMMENTS: PANEL WAS INSTALLED
 
(2) 01/09/2015 01/20/2015 NRS C R (50) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z147320
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
14 AWG USED FOR BRACH CIRCUIT WIRING. AMEND 210
RSLV 12/26/2014 12/26/2014 01/09/2015
 
002 (999) OTHER
MULTIWIRE BRANCH CIRCUITS NOT GROUPED IN PANEL. 210.4D
RSLV 12/26/2014 12/26/2014 01/09/2015
 
003 (999) OTHER
BURNER MOTOR BRANCH CIRCUIT OVER CURRENT PROTECTIVE DEVICE NOT IN-STALLED AS PER MANUFACTURER'S SPEC. FUSE NEEDED. 110.3B
RSLV 12/26/2014 12/26/2014 01/09/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.