BIS Menu  |  DOB Violations  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z147032
Premises: 330 WEST 72 STREET MANHATTAN BIN: 1030970     Block: 1183   Lot: 46
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 330 W 72 ST Census Tract:   159 Health Area:  3900
8A AND 12A Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   RIVERSIDE DRIVE,    RIVERSIDE BOULEVARD
Status:   A - ASSIGNED TO INSPECTOR FPY 03/18/2025 1:25 PM
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/17/2014 8:48 AM
Application Entered:   11/17/2014 Job Start Date:   11/17/2014
Last Change:   03/18/2025 Job End Date:   02/17/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   APPOINTMENT SCHEDULED - CONFIRMATION: 0318Z
Last Inspection By:   JAWORSKI MARCIN       On     04/14/2023      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010346 Licensee Name: PHILIP A ROBINSON
Firm: 001157 Firm Name: PHILIP A. ROBINSON
Firm Phone: 718-783-6542  Firm Address: 43-49 10TH STREET.SUITE 107 LONG ISLAND CITY NY 11101-6999 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $123.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANTHONY BENTEN
Owner Business Name: 33072 OWNERS CORP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  100 AMPS
B. 101 Up to 200 AMPS  1  150 AMPS
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #2 THHN
B. Over #2 to 1/0  1  3/0 THHN
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
008  8A                   
012  12A                   
Buildings Total                     
Total Units : 4 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 0 #10-Wire 0
Existing Meters 2 + New Meters 2 - Removed Meters 2 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 11/17/2014 Notice: 1 - FIRST NOTICE 04/14/2023
Power Issued: 11/17/2014 Response:  

Follow-Up:
Contractor's Comments:  RISERS TO EACH APARTMENT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z147032
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/14/2023 04/14/2023 MJK V (45) (3)
INSPECTION COMMENTS: FAIL, INSPECTION COMPLETE, OBJECTIONS ISSUED, AS PER CONTRACTOR AND OWNERS OF APARTMENTS CONTRACTOR DID ONLY MAIN FEEDERS FOR APARTMENTS UNDER THIS APP. GENERAL WIRING FOR APARTMENT 8A DONE UNDER APP#Z142330. ATOI SEBASTIAN.

OBJECTION FOR APPLICATION #: Z147032
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)CONTRACTOR NEED TO SIGN AFFIDAVIT TO CERTIFY PROPER SUPPORTING FORVERTICAL RUNS OF MAIN FEEDERS TO 12FL AND 8FL ACCORDING WITH NEC2008 TABLE 300.19(A)
OPEN 04/14/2023 04/14/2023
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(OPEN SPACE)314.28(C) 2" CONDUIT BODY (PULL ELBOW) WITH MAIN FEEDERS MISSINGCOVER
OPEN 04/14/2023 04/14/2023
 
003 (329) OPENINGS TO BE SEALED
(OPEN SPACE)300.21 PENETRATION HOLES THROUGH WHICH MAIN FEEDER IS RUN NOT SEALEDWITH FIRE RESISTANT MATERIAL
OPEN 04/14/2023 04/14/2023



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  DOB Violations  |  Electrical Inspection Work Order  |  Back