| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
5 |
5-100A SWITCH |
| B. 101 Up to 200 AMPS |
1 |
1-200A SWITCH |
| C. 201 Up to 600 AMPS |
1 |
1-600A SWITCH |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
21 |
16-SET(6/3) AND 5-SET#2 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
2 |
2 SET 4/0 |
| D. Over 250 MCM |
1 |
1 SET 500 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
MAIN BREAKER COMBO |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER BSMT: 600 AMP SERVICE SW NEUTRAL BOND REQUIRED.. ART.250.28 |
RSLV |
04/14/2015 |
05/13/2015 |
06/01/2015 |
| |
| 002 |
(999) |
OTHER A) BSMT: METER PANS DISC SWS NEUTRAL BOND NOT REQUIRED.. ART.250.24 |
RSLV |
04/14/2015 |
05/13/2015 |
06/01/2015 |
| |
| 003 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE BSMT: 1 SET 4/0 AWG FEEDER FUSE AT 400 AMP |
RSLV |
04/14/2015 |
05/13/2015 |
06/01/2015 |
| |
| 004 |
(999) |
OTHER BSMT: RACEWAYS TO WATER MAIN NOT CONTINUOUS.. ART.250.64 |
RSLV |
04/14/2015 |
05/13/2015 |
06/01/2015 |
| |
| 005 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED BSMT: BRANCH WIRING FROM NEW PANEL |
RSLV |
04/14/2015 |
05/13/2015 |
06/01/2015 |
| |
| 006 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED BSMT: BRANCH WIRING FROM NEW PANEL |
RSLV |
04/14/2015 |
04/14/2015 |
05/13/2015 |
| |
| 007 |
(999) |
OTHER ALL FLOORS APTS PANEL NEUTRAL BOND NOT REQUIRED ART 250.24 |
RSLV |
05/13/2015 |
05/13/2015 |
06/01/2015 |